Troubleshooting
You may see the following messages displayed. Each gives
you specific information about the engine, ECU, or
PowerView.
WAIT TO START PREHEATING - The ECU is
broadcasting a 'Wait to Start' message. Engine
manufacturers typically recommend against starting the
engine while the ECU is broadcasting this message. Once
the ECU stops broadcasting this message, this screen will
no longer be displayed on the PowerView.
CANBUS FAILURE - The PowerView has not received any
valid J1939 CAN messages for at least 30 seconds.
TIMEOUT ECU NOT RESPONDING - The PowerView
sent a request to the ECU for Stored Fault Code (DM2)
information, and the ECU did not respond to the request.
This message on the PowerView indicates the ECU may
not support Stored Fault Code (DM2) functionality over
J1939.