00-02-0795 - 35 - 10-18-11
NO STORED CODES - The PowerView sent a request to
the ECU for Stored Fault Code (DM2) information, and the
ECU responded. There are zero stored codes.
NO GAGE DATA - The PowerView has no record of gages
connected to the RS485 bus.
The following messages are displayed in place of a
parameter value
NO DATA - The PowerView has not received data for the
selected parameter for at least 5 seconds.
NOT SUPPORTED - The ECU is sending a message that
it does not support this parameter.
DATA ERROR - The ECU is sending a message that there
is a data error with this parameter. If not, then specifically
on the PV101, FUEL LEVEL has been selected for display,
and the ANALOG INPUT has been set to FUEL LEVEL, but
no Murphy Fuel Sender has been connected to the analog
input.