EasyManuals Logo

NAiS FPG-C32T2 User Manual

Default Icon
326 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #145 background imageLoading...
Page #145 background image
FPΣ
Communication Cassette
7-12
7.4.2 Tool for Tightening Communication Connector Terminal Block
When tightening the terminals of the communication connector, use a screwdriver
“Phoenix Contact Co., Product No. 1205037, blade size of 0.4 2.5, model No. SZS0,4
x 2,5” or screwdriver “Part No. AFP0806”. The tightening torque should be 0.22 to 0.25
N
m or less.
7.4.3 Wiring Method
Procedure:
1. Remove a portion “7 mm/0.276 in.” of the wire’s insulation.
7mm
Figure 137: FPΣ Communication connector wiring method 1
2. Insert the wire into the terminal block until it contacts the
back of the block, and then tighten the screw clockwise to
fix the wire in place.
Figure 138: FPΣ Communication connector wiring method 2
7.4.4 Cautions Regarding Wiring
The following items should be observed, taking care not to cut or disconnect the wiring.
- When removing the wire’s insulation, be careful not to scratch the core wire.
- Do not twist the wires to connect them.
- Do not solder the wires to connect them. The solder may break due to vibration.
- After wiring, make sure stress is not applied to the wire.
- In the terminal block socket construction, if the wire closes upon counter-clockwise
rotation, the connection is faulty. Disconnect the wire, check the terminal hole, and
then re-connect the wire.
CORRECT
(Clockwise)
INCORRECT
(Counter clockwise)
Figure 139: Cautions regarding wiring

Table of Contents