National Instruments NI 9375 - Safety Voltages

National Instruments NI 9375
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
way. If the product is damaged, return it to NI for
repair.
Safety Voltages
Connect only voltages that are within the following limits:
Channel-to-COM or
Vsup-to-COM
30 VDC maximum
Isolation
DI bank-to-DO bank 60 VDC maximum
Channel-to-Channel No isolation between channels
Channel-to-earth ground
Continuous 60 VDC,
Measurement Category I
Withstand 1,000 Vrms, verified by a 5 s
dielectric withstand test
Measurement Category I is for measurements performed on
circuits not directly connected to the electrical distribution system
referred to as MAINS voltage. MAINS is a hazardous live
electrical supply system that powers equipment. This category is
for measurements of voltages from specially protected secondary