way. If the product is damaged, return it to NI for
repair.
Safety Voltages
Connect only voltages that are within the following limits:
Channel-to-COM or
Vsup-to-COM
30 VDC maximum
Isolation
DI bank-to-DO bank 60 VDC maximum
Channel-to-Channel No isolation between channels
Channel-to-earth ground
Continuous 60 VDC,
Measurement Category I
Withstand 1,000 Vrms, verified by a 5 s
dielectric withstand test
Measurement Category I is for measurements performed on
circuits not directly connected to the electrical distribution system
referred to as MAINS voltage. MAINS is a hazardous live
electrical supply system that powers equipment. This category is
for measurements of voltages from specially protected secondary
NI 9375 Getting Started Guide | © National Instruments | 3