May be due toDescriptionAlarm text on the displayAlarm
Low flow during heating operation
Too high set temperatures
Too high temperature out from the condens-
er. Self-resetting.
High condenser out162
Temperature generated by another heat
source
Too high temperature into the condenser.
Self-resetting.
High condenser in163
Set when the heat pump runs the defrost-
ing procedure
Not an alarm, but an operating status.Defrosting in progress183
Insufficient air circulation or blocked heat
exchanger
Open circuit or short circuit on input for
high pressure switch (63H1)
Defective high pressure switch
Expansion valve not correctly connected
Service valve closed
Defective control board in AMS 10
Low or no flow during heating operation
Defective circulation pump
Defective fuse, F(4A)
The high pressure switch (63H1) deployed
5 times within 60 minutes or for 60 minutes
continuously.
HP alarm220
Open circuit or short circuit on input for
low pressure sensor
Defective low pressure sensor (LPT)
Defective control board in AMS 10
Open circuit or short circuit on input for
suction gas sensor (Tho-S)
Defective suction gas sensor (Tho-S)
Too low a value on the low pressure sensor
(LPT) 3 times within 60 minutes.
LP alarm221
Any circuit breakers for AMS 10 off
Incorrect cable routing
Communication between the control board
and the communication board is interrup-
ted. There must be 22 volt direct current
(DC) at the switch CNW2 on the control
board (PWB1).
OU Com. error223
The fan cannot rotate freely
Defective control board in AMS 10
Defective fan motor
Control board in AMS 10 dirty
Fuse (F2) blown
Deviations in the fan speed in AMS 10.Fan alarm224
Sensor does not work (see section
"Communication connection")
Insufficient air circulation or blocked heat
exchanger
If the fault persists during cooling, there
may be an insufficient amount of refriger-
ant.
Defective control board in AMS 10
Temperature deviation on the hot gas
sensor (Tho-D) twice within 60 minutes or
for 60 minutes continuously.
Continuously high hot gas230
NIBE AMS 10Chapter 9 | Alarm list34
9 Alarm list