EasyManua.ls Logo

Nibe F1145 5 - System Draining Procedures

Nibe F1145 5
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
For more information about the different parts of the
start guide, see page 26.
Menu 5.8 - quick start
It is possible to start the compressor from here.
Caution
There must be a heating or hot water demand
to start the compressor.
Caution
Do not quick start the compressor too many
times in succession over a short period of time
as this may damage the compressor and its an-
cillary equipment.
Menu 5.9 - floor drying function
length of period1-3,5-7
Setting range: 0 - 30 days
Default value: 2 days
temp. period1-3,5-7
Setting range: 15 - 70 °C
Default value:
20 °Ctemp. period 1
30 °Ctemp. period 2
40 °Ctemp. period 3
40 °Ctemp. period 5
30 °Ctemp. period 6
20 °Ctemp. period 7
length of period 4
Setting range: 0 - 30 days
Default value: 3 days
temp. period 4
Setting range: 15 - 70 °C
Default value: 45 °C
Set the function for under floor drying here.
You can set up to seven period times with different cal-
culated flow temperatures. If less than seven periods are
to be used, set the remaining period times to 0 days.
Mark the active window to activate the under floor drying
function. A counter at the bottom shows the number of
days the function has been active. The function counts
degree minutes as during normal heating operation but
for the flow temperatures that are set for the respective
period.
NOTE
During floor drying the heating medium pump
in 100% runs regardless of the setting in menu
5.1.10.
TIP
If operating mode "add. heat only" is to be
used, select it in menu 4.2.
For a more even flow temperature the addition
can be started earlier by setting "start for addi-
tion" in menus 4.9.2 to -80. When set under
floor drying periods have stopped, reset the
menus 4.2 and 4.9.2 as per previous settings.
Menu 5.10 - change log
Read off any previous changes to the control system here.
The date, time and ID no. (unique to certain settings) and
the new set value is shown for every change.
NOTE
The change log is saved at restart and remains
unchanged after factory setting.
NIBE™ F1145Chapter 8 | Control - Menus62