NOTE
Always communicate the product's serial number (14 digits) when report-
ing a fault.
Troubleshooting
If the operational interference is not shown in the display the following
tips can be used:
Basic actions
Start by checking the following possible fault sources:
The switch's position.
Group and main fuses of the accommodation.
The property's earth circuit breaker.
Correctly set load monitor (if installed).
Low hot water temperature or a lack of hot water
Closed or choked filling valve for the hot water heater.
Open the valve.
Heat pump in incorrect operating mode.
If mode "manual" is selected, select "addition".
Large hot water consumption.
Wait until the hot water has heated up. Temporarily increased hot
water capacity (temporary lux) can be activated in menu 2.1.
Too low hot water setting.
Enter menu 2.2 and select a higher comfort mode.
Too low or no operating prioritisation of hot water.
Enter menu 4.9.1 and increase the time for when hot water is to be
prioritised.
Low room temperature
Closed thermostats in several rooms.
Set the thermostats to max in as many rooms as possible. Adjust the
room temperature via menu 1.1 instead of choking the thermostats.
Heat pump in incorrect operating mode.
Enter menu 4.2. If mode "auto" is selected, select a higher value on
"stop heating“ in menu 4.9.2.
If mode "manual" is selected, select "heating". If this is not enough,
select "addition".
Too low set value on the automatic heating control.
NIBE™ F1255Chapter 4 | Disturbances in comfort68