Technical specifications
F2025-14F2025-10F2025-8F2025-6Type
12.9/3.89.4/2.58.1/2.15.9/1.6(kW)Delivered/supplied power* at 2/35 °C **
14.6/3.910.9/2.79.3/2.26.8/1.5(kW)Delivered/supplied power* at 7/35 °C **
10.0/4.17.1/2.75.8/2.34.3/1.8(kW)Delivered/supplied power* at -7/45 °C **
11.9/4.38.6/2.97.3/2.45.3/1.8(kW)Delivered/supplied power* at 0/45 °C **
14.2/4.510.4/3.08.8/2.66.4/1.8(kW)Delivered/supplied power* at 7/45 °C **
9.8/4.56.8/2.95.7/2.54.1/2.3(kW)Delivered/supplied power* at -7/50 °C **
12.4/4.88.9/3.27.4/2.75.4/2.0(kW)Delivered/supplied power* at 2/50 °C **
14.2/5.010.1/3.28.6/2.86.3/2.1(kW)Delivered/supplied power* at 7/50 °C **
16.6/5.111.8/3.310.1/2.97.6/2.1(kW)Delivered/supplied power* at 15/50 °C **
7.0/4.25.0/2.84.1/2.33.1/2.0(kW)Delivered/supplied power* at -20/50 °C **
30271917(A)Starting current
11975(A)Motor protection setting
included as standardSoft-start relay
400 V 3NAC 50HzOperating voltage
Scroll compressorCompressor
0.340.250.200.16(l/s)Nominal flow heating medium
4.42.21.51.3(kPa)Internal pressure drop at nominal flow
0.5/2.5(bar)Min-/max pressure heating medium side
2250/30501700/20001700/2000
1500(m
3
/h)Airflow
180/23090/13090/13070(W)Nominal output, fan
16161010(A)Fuse
IP 24Enclosure class
58585858(°C)Max outgoing heating medium temperature
2.32.22.22.0(kg)Refrigerant volume (R404A)
G1 28 mm)Connection heating medium male Ø
hot gas defrostingDefrosting system
29(bar)Cut-out value pressostat HP
0.3(bar)Cut-out value pressostat LP
-7(bar)Difference pressostat HP
+0.7(bar)Difference pressostat LP
1045(mm)Height with stand
1200(mm)Width
520(mm)Depth
140132126120(kg)Weight
dark greyColour
-20/50 (-7/58)(°C)Lowest operational point, outdoor air/flow line
35/58(°C)Highest operational point, outdoor air/flow line
064 052064 049064 048064 047Part No.
Compressor, fan and control. Flows according to EN 255.
Defrosting reduces the relationship between input/output
by about 10 %.
*
outside temperature/Flow temperature**
45F2025
Miscellaneous
Technical specifications

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibe F2025 and is the answer not in the manual?

Nibe F2025 Specifications

General IconGeneral
BrandNibe
ModelF2025
CategoryHeat Pump
LanguageEnglish

Related product manuals