HIGH ROOM TEMPERATURE
Incorrect settings in indoor module or control module.
See the manual for the indoor module or control
module.
ICE BUILD-UP IN THE FAN, GRILLE AND/OR
FAN CONE ON THE OUTDOOR MODULE
Activate "de-icing fan" (menu 5.11.1.1).
Check that the air flow across the evaporator is cor-
rect.
LARGE AMOUNT OF WATER BELOW F2120
KVR 10 is required.
If KVR 10 is installed, check that the water drainage
flows freely.
NIBE F2120Chapter 8 | Disturbances in comfort40