Low hot water temperature or a lack of hot water
This part of the fault-tracing chapter only applies if the heat pump is docked
to the hot water heater.
Large hot water consumption.
Wait until the hot water has heated up.
Incorrect settings indoor module or control module.
See the manual for the indoor module or control module.
Clogged particle filter.
Check whether alarm high condenser out (162) is in the alarm log.
Check and clean the particle filter.
Low room temperature
Closed thermostats in several rooms.
Set the thermostats to max in as many rooms as possible.
External switch for changing the room heating activated.
Check any external switches.
Incorrect settings in indoor module or control module.
See the manual for the indoor module / control module (VVM / SMO).
Incorrectly adjusted flow across the heat pump.
Check whether alarm high condenser in (163) or high condenser out
(162) is in the alarm log. Follow the instructions for adjusting charge
flow.
High room temperature
External switch for changing the room heating activated.
Check any external switches.
Incorrect settings in indoor module or control module.
See the manual for the indoor module or control module.
F2120 not in operation
F2120 communicates all alarms to the indoor module/control module
(VVM / SMO).
Ensure that the F2120 is connected to the power source.
Check the indoor module/control module (VVM / SMO). See section
"Disturbances in comfort" in the Installer Manual for the indoor mod-
ule/control module (VVM / SMO).