EasyManua.ls Logo

Nibe S1156 - Cooling Module Removal Steps

Nibe S1156
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NOTE
Switch off the heat pump and cut the power with
the safety switch.
Caution
Remove the front cover according to the descrip-
tion on page 8.
1. Close the shut-off valves (EP14-QM31), (EP14-QM32),
(EP14-QM33) and (EP14-QM34).
Drain the compressor module according to the instruc-
tions on page 63
UN
EP14-QM34
EP14-QM31
EP14-QM32
EP14-QM33
2. Remove the insulation.
3. Remove the locking plate.
4. Disconnect the pipe connection under the shut-off valve
(EP14-QM31).
5. Remove the two screws.
6. Disconnect the connectors (XF2), (XF11) and (XF22).
7. Carefully pull out the cooling module.
XF22 XF2 XF11
TIP
The cooling module is installed in reverse order.
NOTE
During reassembly, the enclosed O-rings should
replace the existing ones on the shut-off valves
(EP14-QM32), (EP14-QM33) and (EP14-QM34).