EasyManua.ls Logo

Nibe SMO 20 - Cooling Settings; Delta Temperature Settings

Nibe SMO 20
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
cooling settings (heat pump with cooling function required)
cooling1.9.5
delta at +40 °C
delta at +20 °C °C
°C
°C
DM
heat/cool sen.
heat at room under temp.
set pt value cool/heat sensor
BT74
cooling1.9.5
set pt value cool/heat sensor
heat at room under temp.
cool at room over temp.
use room sensor
°C
°C
°C
delta at +20 °C
Setting range: 3 10 °C
Factory setting: 3
delta at +40 °C
Setting range: 3 20 °C
Factory setting: 6
Menu
1.9.5
heat/cool sen.
Setting range: BT74 (BT50, RMU-BT50)
Factory setting: BT74
set pt value cool/heat sensor
Setting range: 5 40 °C
Factory setting: 21
heat at room under temp.
Setting range: 0.5 10.0 °C
Default value: 1.0
cool at room over temp.
Setting range: 0.5 10.0 °C
Default value: 3.0
35NIBE™ SMO 20Chapter 3 | SMO 20 at your service

Other manuals for Nibe SMO 20

Related product manuals