20 VEDEX 4000
6 General information for the installer
Boiler room
Distance to walls
Assembly
Carbon Monoxide Detectors
Chimney
VEDEX 4000 has inlets for primary and secondary air on
the sides of the boiler. Therefore, always leave a space of
at least a metre from combustible material. In unfavoura-
ble cases “pu󰀨s” from combustion can discharge sparks.
It is mandatory to t a Carbon Monoxide alarm within
the room whenever a new or replacement solid fuel
appliance is installed in a dwelling. This alarm must
be a permanently installed type, rather than a porta-
ble type, and should incorporate self-test and audible
alert if the battery or detector cell develop a fault.
Setting of the alarm must meet the following criteria:
on the ceiling at least 300mm from any wall or,
if it is located on a wall, as high up as possible
(above any doors and windows) but not within
160mm of the ceiling;
between 1m and 3m horizontally from the appliance.
Many older boilers have the ue duct located at the
bottom and have been connected to the chimney
near to the oor. If the new boiler is to be connected
higher up on the chimney the lower, non-active, part
of the chimney pipe should be lled with sand or sim-
ilar material.
Material Area Min. height
Steel pipe Ø160 mm 5.0 m
Brick 160 x 160 mm 5.0 m
The boiler room must be built in accordance with ap-
plicable building regulations.
Provision for good air supply. The boiler room’s air
intake must be as large as the ue.
Set the boiler while maintaining the minimum distances
to the walls. When installing the unit, pay special atten-
tion to a convenient access to the boiler and chimney
during maintenance, cleaning and servicing.
1 - foundations
Ensure that sweeping can be carried out in
accordance with the applicable regulations.
If in doubt, contact a chimney sweep.
NOTE
VEDEX 4000 has a vertical ue pipe connection with
an external diameter of 133mm. A vertical ue pipe is
supplied as standard.
The ue diameter should be 160mm in accordance
with the Building Regulations.
The ue should be dimensioned in accordance with
the Building Regulations and EN 13384-1 to facilitate
correct functioning of the combustion system.
The minimum chimney draught for satisfactory wood
ring is 15 Pa. The ue needs to be inspected and
approved before installation.
Dimension Distance [mm]
A 1000
B 600
C 600
D 600
E 1000
F 150
1
B
D
A
E
F
C