32 FIRE
33 GND
contact must be shorted to ground through a switch to open the gate.
The FAIL SAFE connector which is shorted at the factory with a jumper
(Normally
Closed NC), may be wired in parallel with the Fire input to release the
a power failure. Opening the FAIL SAFE contacts allows the gate to be
pushed open by hand.
9.4 - EXIT & EDGE INPUTS WIRING DIAGRAM
28 EDGE
29 GND
30 EXIT
31 GND
(NC or NO) input. The EDGE sensor input is intended for ANSI/UL 325 listed
gate edge sensors to protect against entrapment and hazardous pinch points
along the moving edge of the closing gate. The EXIT sensor input is provided
to activate to open the gate, or re-open a closing gate, upon sensing an exiting
vehicle.
9.2 - MAGNETIC LOCK CONNECTION
7 NC
8 Com (Common)
9 NO
10 GND
11 V+ (Voltage is determined by incoming power supply)
This connection is used to install the magnetic lock. In this instance a gate
can be locked magnetically to prevent a forced opening. Consult lock
34 OPEN
35 STOP
36 CLOSE
37 GND
Wi
th the Guard Station switches installed, the user can operate the gate
espective buttons for the command that is desired. Gate
e controlled by NORMALLY OPEN (NO) and Stop is
rolled by NORMALLY CLOSED (NC) momentary switches.
If the guard station inputs are not used
Exit Device
9.1 - FIRE DEPARTMENT CONNECTION
FIGURE 9 -1 FIRE DEPARTMENT INPUT
FIGURE
9 -2 MAGNETIC LOCK WIRING (EXAMPLE)
9.3 - GUARD STATION
FIGURE 9 -3 GUARD STATION INPUTS
FIGURE 9 - 4 EXIT AND EDGE INPUTS
15