FURTHER DETAILS AND DIAGNOSTICS
10.1 - Further details
10.1.1 - Signals when switching ON
WhentheDPRO500controlunitisswitchedON,thereactionofthegreenOK
L2 led andthe red WARNING L1 LED is important,as shown in Table4.In
particular,itindicateswhether:
- The recognition of the Opening and Closing positions is correct;
- The recognition of the (sensitive edge) safety device is correct and what kind
of safety device has been recognised.
TABLE 4
Signals when
switched on
Signal
GREEN OK
L2 LED
RED WARNING
L1 LED
Blank memory (no acquired
position or safety device)
Rapidashingfor5
seconds
Rapidashingfor5
seconds
Positions acquired correctly
and“8k2”safetyrecognised
Rapidashingfor2
seconds
Justoneslowash
Positions acquired correctly
and“OSE”safetydevice
recognised
Rapidashingfor2
seconds
Twoslowashes
AfterprovidingthesignalsshowninTable4,theDPRO500 controlunitshows
anyerrorsthroughDiagnosticsusingtheOKL2ledandtheWARNINGL1LED.
10.1.2 - Other functions
Status and diagnostics indicator (terminal on the keyboard)
The control unit allows you to connect a24V-5W max. indicator light to the
“indicator”terminalonthepushbuttonpanelhousedinsidetheboxcover(Fig.
21:terminal1-, 2 +). The “indicator” can beinstalledonthecoveritself,by
making a hole on the latter, or it can be installed outside the control unit at a
maximumdistanceof2mfromthelatter.
CAUTION! - The output is not protected against short-circuits.
This“indicator”functionsinthefollowingway:
- off when the safety chain is open (ALT inp, red STOP button, thermal protec-
tion or release)
- ashes0.5sON,0.5sOFFwhenitworksproperly
- showsthesamediagnosticsastheredL1WARNINGLEDwhenthereare
“seriouserrors”(Paragraph10.2).
Setting the pause time for automatic closing
1 SetDIPswitches3and4toON.
2 Send a command to open the gate so as to move the gate to its fully open
position.
3 Once this position is reached, wait for a period of time equal to the required
pause time for automatic closing and then command the gate to close. The
pause time for automatic closing is now saved.
Inordertochangethepausetime,setdip3and4toOFFandthenbacktoON.
At this point you must repeat the sequence of opening, pause time and closing.
CAUTION! - WhenDIPswitch4ismovedtotheOFFposition,thepausetime
is deleted.
10.2 - Diagnostics
Some devices are equipped to display messages to identify their status and faults. The following table describes the various alarm signals according to the type
ofproblem.ThesealarmsignalsareprovidedbyappropriateashesofthegreenOKL2LEDandtheredWARNINGL1LEDandfromtheashinglight(ifthere
is one) connected to the specially programmed control unit outputs.
DIAGNOSTICS GREEN OK L2 LED
Signal Cause Solution Flashing light
2ashes-shortpause
2ashes-longpause
Triggering of a photocell
At the start of the manoeuvre, one or more photocells fail to give the
enable signal; check for obstacles and whether the photocells are in-
terferingwitheachother’sIR.Whenthesafetydeviceshaveintervened,
the automation can be controlled with a person present through the
wired controls. It is not possible to send commands via radio.
Flash
4ashes-shortpause
4ashes-longpause
Triggering of the STOP input
At the start of or during the manoeuvre, the STOP or ALT input was
triggered; identify the cause. When the safety devices have intervened,
the automation can be controlled with a person present through the
wired controls. It is not possible to send commands via radio.
Flash
6ashes-shortpause
6ashes-longpause
Manoeuvre limiting device --- Flash
9ashes-shortpause
9ashes-longpause
Automation system locked Sendthe“ReleaseAutomation”commandorcommandthe
manoeuvrewith“Step-by-StepHighPriority”.
Flash
TheLEDscomeonfor3
seconds
Lock automation --- Flash
2ashesof1secondwith
pause of 1.5 seconds
Automation system released --- Flash
DIAGNOSTICS RED WARNING L1 LED
Certain signals can be cancelled by pressing the red STOP button
Signal Cause Solution Flashing light
5ashes-shortpause
5ashes-longpause
EEPROMerror-Errorinthe
internal parameters of the control
unit
Disconnect and reconnect the power supply. If the error persists, run
the“Totaldeletionofthecontrolunitmemory”(paragraph7.8)and
rerun installation. If the condition persists, there may be a serious
fault and you will need to replace the electronic circuit board.
Flash
2ashes-shortpause
2ashes-longpause
Safety Test Error Reruntherecognitionprocedureforthesafetydevicesconnectedto
thecontrolunit(paragraph7.9).
---
3ashes-shortpause
3ashes-longpause
Error in direction of rotation
of the Encoder Or inverted limit
switch
ReversethedirectionofrotationoftheencoderbymovingDIPswitch
2toON(seeparagraph7.10).Ifthemotormountsamechanicallimit
switch, reset the error by pressing the STOP button and invert the
opening limit switch connection with that of the closing limit switch
at the LIMIT SWITCH terminal (Fig. 14).