NORDAC FLEX (SK 200E ... SK 235E)Users Manual for Frequency Inverters
120 BU 0200 en-3118
Pos: 26 3.6 /A nleitu ngen/ Elektr onik /FU und St art er/4. In betri ebnah me/AS-I nt erf ace [ all e G erät e]/ Mer kmal e u nd T ech nisc he Dat en_ 01 [ SK 1 xxE, SK 2xxE, SK xxxE-FDS] @ 1\mod_1345713871281_388.docx @ 39088 @ 3 @ 1
4.5.2 Features and technical data
The device can be directly integrated in an AS interface network is parametrised in its factory settings
so that the most frequently used AS-i functionality is available immediately. Only adaptations for
application-specific functions of the device or the bus system, the addressing and proper connection of
the supply, BUS, sensor and actuator cables need to be carried out.
Pos: 263. 7 / Anlei tu ngen /El ektr oni k/FU un d Start er/4 . Inbetri ebn ahme/ AS-Int erf ace [ all e G erät e]/ Mer kmal e u nd T ech nisc he Dat en_ 02 [ SK 2 xxE ] @ 9\mod_1443515373484_388.docx @ 247303 @ @ 1
Features
Electrically isolated bus interface
Status display (1 LED) (SK 225E and SK 235E only)
Configuration optionally via
Integrated potentiometer and DIP switch
Or by means of parametrisation
24 V DC supply of integrated AS-i module or AS-i line
24 V DC supply of frequency inverter
Via yellow AS-i line (SK 225E and SK 235E only, but not special versions SK 2x5E-…-AUX and -AXB)
Via black line or another 24 V DC source e.g. SK xU4-24V-… power supply (special versions
SK 2x5E-…-AUX and -AXB only)
Connection to device
Via terminal block
Or via M12 flanged connector
Pos: 263. 8 / Anlei tung en/El ektr onik/F U und St arter/ 4. Inbetr ieb nahm e/AS-I nter fac e [ alle Ger äte] /Mer k male und Te chni sc he Da te n_0 3 [SK 2xx E] @ 6 \mod_1415706292381_388.docx @ 186296 @ 5 @ 1
Technical data for AS interface
Designation
Value
SK 220E / SK 230E
SK 225E-…-AXB
SK 235E-…-AXB
SK 225E / SK 235E SK 225E-…-AUX
SK 235E-…-AUX
AS-i supply, PWR connection 24 V DC, max. 25 mA
26.5 3.,6 V DC,
max. 290 mA
1)
24 V DC,
max. 25 mA
Slave profile
S-7.A
S-7.0
I/O-Code 7 7
ID Code
A
0
External ID Code 1 / 2 7 F
Address
1A – 31A and 1B - 31B
(Delivery condition 0A)
1 31
(Delivery condition: 0)
Cycle time
Slave
Master ≤ 10 ms
Master Slave ≤ 21 ms
5 ms
Quantity of BUS I/O 4I / 4O 4I / 4O
1)
Of which 60 mA available for peripherals (initiators, connected parametrisation tool, actuators)