5 Parameter
BU 0200 en-3118 165
Pos: 41 9 /Anlei tung en/El ektr onik/FU und Star ter/5 . Par amet er/ Par amet erau fli st ung (P 000 .. .)/P 400- P499 /Par amet er P400 F kt. S oll wer tei nga ng [S K 2x5E ] @ 2\mod_1346931796285_388.docx @ 42354 @ @ 1
P400 [-01]
...
[-09]
Function Setpoint inputs
(Function of setpoint inputs)
SK 2x5E
P
0 ... 36
{ [-01] = 1 }
{ [-02] = 15 }
{ [-03] = 0 }
{ [-04] = 0 }
{ [-05] = 1 }
{ [-06] = 0 }
{ [-07] = 1 }
{ [-08] = 0 }
{ [-09] = 0 }
[-01]
Potentiometer 1, Function of the potentiometer P1 integrated into the FI. DIP switches 4/5
must be "Off" so that the function can be influenced by this parameter setting
(chapter
4.3.2.2)
[-02]
Potentiometer 2, as for potentiometer 1
[-03]
External Analogue input 1, AIN1 of the first I/O extension (SK xU4-IOE)
[-04]
External Analogue input 2, AIN2 of the first I/O extension (SK xU4-IOE)
[-05]
Setpoint module
[-06]
Digital input 2, can be set to pulse signal evaluation via parameter P420 [-02] =26 or 27.
The pulses are then evaluated in the FI as an analogue signal according to the function
which is set here.
[-07]
Digital input 3, can be set to pulse signal evaluation via parameter P420 [-03] =26 or 27.
The pulses are then evaluated in the FI as an analogue signal according to the function
which is set here.
[-08]
External A.in. 1 2nd IOEE,
"External analogue input 1 2nd IOE"
, AIN1 of the second I/O
extension (SK xU4-IOE) (= Analogue input 3)
[-09]
External A.in. 2 2nd IOE, "External analogue input 2 2nd IOE", AIN2 of the second I/O
extension (SK xU4-IOE) (= Analogue input 4)
The basic versions of the SK 2x5E devices do not have an analogue input. An analogue function
can only be used by using options (array [-01]...[-05] and [-08]…[-09]) or using digital input 2 or 3
(array [-06]...[-07]).
... Setting values below.
Pos: 42 0 /Allg emein/ Allg emeing ültig e Mod ule/---------Sei tenumbr uch ko mpakt --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1

Table of Contents

Other manuals for Nord Drivesystems NORDAC FLEX SK 205E Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nord Drivesystems NORDAC FLEX SK 205E Series and is the answer not in the manual?

Nord Drivesystems NORDAC FLEX SK 205E Series Specifications

General IconGeneral
SeriesNORDAC FLEX SK 205E
CategoryInverter
Protection ClassIP20
Braking ResistorOptional
Power Range0.25 to 22 kW
Input Voltage3 × 380 – 480 V
Output VoltageThree-phase 0 to input voltage
Control ModeV/f control, vector control
Communication InterfacesRS485, CANopen, PROFIBUS
Frequency Range0 to 600 Hz
Cooling MethodNatural convection
Ambient Temperature Range-10 °C to +40 °C
Storage Temperature Range-25 °C to +70 °C
Relative Humidity95% (non-condensing)
Installation AltitudeUp to 1000 m