1.5 USS - Data transfer
BU 0050 GB-3111 Subject to technical amendments 41
Error messages if the order cannot be executed
If the response label is "Order cannot be executed" (AK = 7), then an error message is added to the
parameter value (PWE2) of the inverter response. For the meanings of the transferred values , please refer
to the following table.
Parameter value cannot be changed
Lower or upper value limit exceeded
Only resettable (only 0 may be written)
Description element cannot be changed
Description data not present
Invalid order element in the last order received
Internal response label cannot be depicted
1.5.4.2 Sub-index (IND)
The structure and function of the parameter index (IND) depends on the type of parameter to be transferred.
For values which depend on the parameter set, the parameter set can be selected via Bits 0 and 1 of the
Index (IND) (0 = parameter set 1, 1 = parameter set 2,...).
If the parameter to be processed is also an array parameter (e.g. position array for the POSICON option),
then the sub-index of the required parameter can additionally be accessed via Bit 2 to Bit 7 of the sub-index
(0 = array element 1, 1 = array element 2,…):
If a parameter is not dependent on the parameter set, then Bits 0 -7 are used for the sub-index.
Please refer to the operating instructions for details of the structure of the individual parameters and which
values may be called up.