NORD USS and Modbus RTU Manual
66 Subject to technical amendments BU 0050 GB-3111
2.5.5 06h Write Single Register
Enables writing of a single 16Bit parameter.
Master Slave
Slave Master
Function Code
1 Byte
0x06
Function Code
1 Byte
0x06
Address
2 Byte
0x0000 to 0xFFFF
Address
2 Byte
0x0000 to 0xFFFF
Parameter Value
2 Byte
0x0000 to 0xFFFF
Parameter Value
2 Byte
0x0000 to 0xFFFF
Example:
Parameter P102, parameter set 2 is written with the value 0x0123 (see also the item "Parameter access" in
Section 2.8 Description of parameters).
Query (Master Slave)
Response (Slave Master)
Address
0x08
Address
0x08
Function Code
0x06
Function Code
0x06
Address High
0x19
Address High
0x19
Address Low
0x81
Address Low
0x81
Parameter value High
0x01
Parameter value High
0x01
Parameter value Low
0x23
Parameter value Low
0x23
CRC High
0x9E
CRC High
0x9E
CRC Low
0x6E
CRC Low
0x6E
2.5.6 10h Write Multiple Register
This command enables several parameters to be written consecutively, and for parameters with a data length
of 32Bit.
In the process data area, all process data of the P050 parameter array can be written simultaneously.
If parameters are written with this access, only a single parameter can be written with a telegram. This access
is used to write 32Bit parameters.
NOTE
The parameter (P050) "Process data IN" and (P051) "Process data OUT" are executed in the
background and are not visible to the user. From a structural point of view, these are array
parameters ([-01 -04]). Assignment of the setpoints in parameter (P050) is carried out via
the parameters (P546 (… P548)). The return of the actual values in parameter (P051) is
assigned in parameters (P543 (… P545)).
Master Slave
Slave Master
Function Code
1 Byte
0x10
Function Code
1 Byte
0x10
Start address
2 Byte
0x0000 to 0xFFFF
Start address
2 Byte
0x0000 to 0xFFFF
Number of
parameters
2 Byte
0x0001 to 0x0004
Number of parameters
2 Byte
0x0001 to 0x0004
Number of bytes
1 Byte
0x01 to 0x08
Parameter Value
N*2 Byte