EasyManua.ls Logo

Nord Drivesystems SK 700E Series - 3.2 Error messages

Nord Drivesystems SK 700E Series
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NORD USS and Modbus RTU Manual
72 Subject to technical amendments BU 0050 GB-3111
3.2 Error messages
Table of possible bus-specific error messages
Display
in the ControlBox
Fault
Text in the ParameterBox
Cause
Remedy
Group
Details in
P700 / P701
E010
10.0
(Bus Timeout)
Telegram timeout, data transfer is faulty. Check P513.
Check external Bus connection.
Check bus protocol program process.
Check Bus Master.
10.2
Bus Timeout Option
Telegram timeout for external bus module,
telegram communication is faulty.
Check external connection.
Check bus protocol program process.
Check Bus Master.
10.4
Init error Option
External bus module initialisation failure
Check P746.
Bus module not correctly plugged in.
Check Bus module current supply.
10.1
System error option
External Bus module system failure
10.3
10.5
10.6
10.7
10.8
Error option
Communication error in external module
connection error/fault in external module

Related product manuals