NORD USS and Modbus RTU Manual
44 Subject to technical amendments BU 0050 GB-3111
1.6.2 Switch-on block Standby
A frequency inverter with the USS address 0 is to be switched from the status "Switch-on disabled"
(STW Bit 0 – 0), which is active when the device is switched on, to the "Standby" status (STW Bit 0 = 1).
Parameter set 1 is valid and no parameter data is transfered.
Procedure:
Check last status word (ZSW 0A 70)
Set address (Address 00)
Generate control word (STW 04 7E)
Send telegram
Check response telegram (ZSW 0B 31)
Details:
The status word of frequency inverter is in switch-on block status
Reference value undershot
To switch the frequency inverter to the standby status, the following telegram must be sent:
Abbreviations used:
PKW Parameter identifier Value
PZD Process data
PKE Parameter identifier
IND Index
PWE Parameter Value
STW Control word 1
ZSW Status word 1
SW1..3 Setpoint
IW1..3 Actual value