NORD USS and Modbus RTU Manual
58 Subject to technical amendments BU 0050 GB-3111
Parameter
Setting value / Description / Note
Comments
P741 ... [-01]
... [-13]
Process data Bus Out
(Process data Bus Out)
SK 500E to SK 535E
0000 ... FFFF (hex)
This parameter provides
information about the actual
status word and the actual
values that are transferred via
the bus systems.
[-01] = Status word
Status word, source from
P509.
[-02] = Actual value 1 (P543)
[-03] = Actual value 2 (P544)
[-04] = Actual value 3 (P545)
[-05] = Bus I/O Out Bit (P481)
The displayed value depicts
all Bus In bit sources linked
with OR.
[-06] = Parameter data Out 1
[-07] = Parameter data Out 2
[-08] = Parameter data Out 3
[-09] = Parameter data Out 4
[-10] = Parameter data Out 5
Data during parameter
transfer.
[-11] = Actual value 1 master
function
[-12] = Actual value 2 master
function
[-13] = Actual value 3 master
function
Actual value of master
function
502/P503.
P741 ... [-01]
... [-23]
Process data Bus Out
(Process data Bus Out)
SK 540E / SK 545E
0000 ... FFFF (hex)
This parameter provides
information about the actual
status word and the actual
values that are transferred via
the bus systems.
[-01] = Status word
Status word, source from
P509.
[-02] = Actual value 1 (P543 [-01])
[-03] = Actual value 2 (P543 [-02])
[-04] = Actual value 3 (P543 [-03])
[-05] = Actual value 4 (P543 [-04])
[-06] = Actual value 5 (P543 [-05])
[-07] = Bus I/O Out Bit (P481)
The displayed value
depicts all Bus In bit
sources linked with OR.
[-08] = Parameter data Out 1
[-09] = Parameter data Out 2
[-10] = Parameter data Out 3
[-11] = Parameter data Out 4
[-12] = Parameter data Out 5
Data during parameter
transfer.
[-13] = Actual value 1 master function
[-14] = Actual value 2 master function
[-15] = Actual value 3 master function
[-16] = Actual value 4 master function
[-17] = Actual value 5 master function
Actual value of master
function
502/P503.
[-18] = Status word PLC
Status word via PLC
[-19] = Actual value 1 PLC
[-20] = Actual value 2 PLC
[-21] = Actual value 3 PLC
[-22] = Actual value 4 PLC
[-23] = Actual value 5 PLC
Actual value data via PLC