NORDAC SK 200E Handbuch
136 Subject to technical alterations BU 0200 GB
Parameter Setting value / Description / Note Device Supervisor
Paramter-
satz
P709 ... - 01
...
... - 07
Analog input values
-100.0 ... 100.0 % Displays the measured analog input value.
[-01] = Potentiometer 1, internal FI potentiometer P1 (Section 4.1.3), for the adjustment
of “maximum frequency”, “minimum frequency” and “ramp time”
[-02] = Potentiometer 2, internal FI potentiometer P2 (Section 4.1.3) with fixed steps, the
function can also be entered via the DIP switch.
[-03] = External analog input 1, of I/O extension SK CU4-/TU4-IOE.
[-04] = External analog input 2, of I/O extension SK CU4-/TU4-IOE.
[-05] = Setpoint module, in preparation
[-06] = Digital input 2, analog function of FI digital input 2
[-07] = Digital input 3, analog function of FI digital input 3
P710 Voltage analog output
0.0 ... 10.0 V Displays the delivered value of analog output.
P711 Output status
00 ... 11 (bin)
or
0 ... 3 (hex)
Displays the actual status of the digital outputs.
Bit 0 = Digital output 1
Bit 1 = Mechanical brake
P714 Operating time
0.00 ... ___ h This parameter shows the time for which the FI was connected to the mains and was ready for
operation.
P715 Run time
0.00 ... ___ h This parameter shows the time for which the FI was enabled and supplied current to the output.
P716 Actual frequency
-400.0 ... 400.0 Hz Displays the actual output frequency.
P717 Actual rotation speed
-9999 ... 9999 rpm Displays the actual motor speed calculated by the FI.
P718 ... - 01
... - 02
... - 03
Actual setpoint frequency
-400.0 ... 400.0 Hz
Displays the frequency specified by the setpoint.
... -01 = Actual setpoint frequency from the setpoint source
... -02 = Actual setpoint frequency after processing in the FI status machine
... -03 = Actual setpoint frequency after the frequency ramp
P719 Actual current
0.0 ... 999.9 A Displays the actual output current.