5.8 Information
BU 0200 GB Subject to technical alterations 137
Parameter Setting value / Description / Note Device Supervisor
Paramter-
satz
P720 Actual torque current
-999.9 ... 999.9 A Displays the actual calculated torque-developing output current (active current). Basis for
calculation are the motor data P201...P209 ... .
negative values = generator, positive values = drive
P721 Actual field current
-999.9 ... 999.9 A Displays the actual calculated field current (reactive current). Basis for calculation is the motor
data P201...P209 ... .
P722 Actual voltage
0 ... 500 V Displays the actual AC voltage supplied by the FI output.
P723 Actual voltage components Ud
0 ... 500 V Displays the actual field voltage component.
P724 Actual voltage components Uq
0 ... 500 V Displays the actual torque voltage component.
P725 Actual cos phi
0.00 ... 1.00
Displays the actual calculated cos
of the drive.
P726 Apparent power
0.00 ... 99.99 kVA Displays the actual calculated apparent power. Basis for calculation is the motor data
P201...P209 ... .
P727 Mechanical power
-99.99 ... 99.99 kW Displays the actual calculated effective power of the motor. Basis for calculation is the motor
data P201...P209 ... .
P728 Mains voltage
0 ... 1,000 V Displays the actual mains voltage at the FI input.
P729 Torque
-400 ... 400 % Displays the actual calculated torque. Basis for calculation is the motor data P201...P209 ... .
P730 Field
0 ... 250 % Displays the actual field in the motor as calculated by the inverter. Basis for calculation is the
motor data P201...P209 ... .