EasyManua.ls Logo

nord sk 200e - Pump Drive - SK 072.1 F-71 S;4 CUS with Motor-Mounted SK 200 E; Overview; Initial Checks Pump Drive

nord sk 200e
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.nord.com
3
Bayer SK200E Troubleshooting Guide – Subject to Change Without Notice
SK 072.1F-71/S4
Motor Mounted SK 200E
Pump Drive - SK 072.1F-71S/4 CUS with Motor-Mounted SK 200E
Overview
ThepumpdriveassemblyconsistsofaNORDBLOC.1
inlinegearboxwitha1/3hpmotor(SK072.1F-71S/4)
andmotor-mountedSK200EACvectordrive.
A 1/3 hp (0.25 kW) rated AC vector drive rated for
1-phase230VACinputismounteddirectlytothe1/3
hp(0.25kW)ratedmotorwhichiswiredforlowvolt-
age(3-phase230VAC).TheSK200EACvectordrive
includes an internal 24VDC control power supply
withouttheneedforanadditionalmodule.Thedrive
assemblyincludes2xanaloginputs,4xdigitalinputs,
and2xdigital outputs. An8-pin M12 quick-discon-
nectreceptacleisprovidedasthemeansofconnect-
ingthecontrolsignalsfromthecontrolpanel.
A4-20mAsignalisconnectedtoananaloginputand
isusedasthespeedreference(0-100Hz).Twoofthe
digital inputs are used to control the Drive Enable
andRotationReversalfunctions.Finally,a24Vdigi-
taloutputisusedtoprovidefeedbacktothecontrol
panelthatthedriveisrunning.
Initial Checks – Pump Drive
Beforeapplyingmainsinputpowertothedrive,per-
formthefollowingchecks:
1) Check the Type and Part Number on the name-
plateoftheACvectordrive.Ifeitherisnotaslisted
below,theACvectordrivedoesnothavethecorrect
ratingandmayneedtobeexchanged.
a.TypeshouldbeSK200E-250-123-A
b.PartNumbershouldbe275226103
2) Accesselectricalconnectionsbyfollowing
procedureshownbelow.
a.ConfirminputACsupplyvoltageisturnedoff.
b.Loosenthe4hexsocketheadscrews(4mm).
c.CarefullylifttheACvectordriveoffthe
connectionunit
d.Theelectricalconnectionsandtheoptionslots
arenowfreelyaccessible.
Type
Part Number
Figure 3 - 1/3HP SK 200E Nameplate
Figure 2 - SK 072.1F-71/S4 & Motor Mounted SK 200E
Controls
4mm hexsocketheadscrews
cinchplugs
TI4motor
adapter
Figure 4 – AC Vector Drive Removal/Installation