Table 8. Charging Table for JT5BD-042K Series (3.5 Ton Units)
Suct.
Press.
OUTDOOR TEMPERATURE (° F)
70 75 80 85 90 95 100 105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
71 144 150
73 146 155 159 152
75 148 161 161 157 175 153
77 152 163 164 162 177 158 191 154
79 155 165 167 164 179 163 193 159 206 156
81 171 167 183 166 195 164 208 160 222 157
83 186 169 198 167 210 165 224 162 237 159
85 202 171 214 169 226 166 239 163 253 160
87 205 174 217 172 229 170 241 167 255 164
89 221 176 233 174 245 171 257 168
91 236 178 248 175 260 172
93 252 180 264 177
95 267 181
97
Table 9. Charging Table for JT5BD-048K Series (4 Ton Units)
Suct.
Press.
OUTDOOR TEMPERATURE (° F)
70 75 80 85 90 95 100 105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
69 132 130
71 134 136 149 135
73 136 141 151 140 166 140
75 137 149 153 145 168 145 183 145
77 140 152 154 152 170 150 185 149 200 149
79 158 155 172 155 188 154 203 153 218 153
81 176 158 190 158 205 158 220 157 235 157
83 193 162 207 162 222 162 237 161 252 161
85 197 166 211 166 225 166 239 165 254 165
87 214 170 229 170 243 170 256 169
89 232 174 246 174 260 174
91 250 178 264 178
93 267 183
95
Shaded boxes indicate fl ooded conditions.
Rated design values. The suction pressure will vary from design value if indoor air fl ow, entering dry bulb,
or entering wet bulb temperatures are lower than design.
1. All pressures are listed in psig and all temperatures in ° F
2. Discharge temperatures greater than charted values indicate an undercharged system.
3. In Cooling Mode suction pressure will be lower than design value if indoor air fl ow, entering dry bulb, or entering
wet bulb temperatures are lower than design.
4. In Heating Mode, charge should be weighed in. It is strongly recommended to verify charge in Cooling Mode
at ambient above 70°F.
REFRIGERANT CHARGING TABLES - COOLING MODE