Table 10. Charging Table for JT5BD-060K Series (5 Ton Units)
Suct.
Press.
OUTDOOR TEMPERATURE (° F)
70 75 80 85 90 95 100 105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
66 143 146
68 145 152 159 149
70 147 157 161 154 175 152
72 148 164 163 159 178 157 192 155
74 152 167 165 165 180 162 194 159 208 157
76 169 168 182 167 196 164 210 161 224 159
78 185 170 198 168 212 166 226 164 240 161
80 202 172 215 170 228 168 242 165 256 163
82 205 175 218 174 232 172 244 169 258 167
84 222 178 235 176 248 174 260 171
86 238 180 252 178 265 176
88 255 182 268 180
90 271 185
92
Shaded boxes indicate fl ooded conditions.
Rated design values. The suction pressure will vary from design value if indoor air fl ow, entering dry bulb,
or entering wet bulb temperatures are lower than design.
1. All pressures are listed in psig and all temperatures in ° F
2. Discharge temperatures greater than charted values indicate an undercharged system.
3. In Cooling Mode suction pressure will be lower than design value if indoor air fl ow, entering dry bulb, or entering
wet bulb temperatures are lower than design.
4. In Heating Mode, charge should be weighed in. It is strongly recommended to verify charge in Cooling Mode
at ambient above 70°F.
REFRIGERANT CHARGING TABLES - COOLING MODE