24 6-050700 X2
212iLW & 242iLW Standalone Keypad
Installation & Programming Manual
7.6 Programming Options Chart – Quick Reference
To enter program mode press 99 # master code ✱.
Command/Action Keys to Enter/Details
Add Standard User
user location # code ✱ code ✱
Add Standard User
with Specifi c Unlock
Time
unlock time # user location # code ✱ code ✱
Add/Modify
Enhanced User
60 # user type # user location # code ✱ code ✱
(refer to Section 7.4 for details)
Delete User
user location # ✱ ✱
Set LOCK Output
Time Duration
11 # time # 0 # ✱ ✱ (1 to 255 seconds)
Enable/Disable
Keypad Options
30 # option # enable/disable # ✱ ✱
(refer to Section 7.5 for details)
Enable/Disable User
56 # enable/disable # user location # ✱ ✱
Assign Virtual
Outputs to Physical
Outputs
10 # virtual output # physical output # ✱ ✱
(refer to Section 7.2 for details)
Program REX
Outputs
49 # output list # 0 # ✱ ✱
Program Users to
Operate OUT2-5
59 # output list # user location # code ✱ code ✱
Set OUT2 Time
Duration
12 # ttt # mmm # ✱ ✱ (refer to page 19 for details)
Set OUT3 Time
Duration
13 # ttt # mmm # ✱ ✱ (refer to page 19 for details)
Set OUT4 Time
Duration
14 # ttt # mmm # ✱ ✱ (refer to page 19 for details)
Set OUT5 Time
Duration
15 # ttt # mmm # ✱ ✱ (refer to page 19 for details)
Set Propped Door
Time
44 # time # 0 # ✱ ✱ (10 to 990 seconds)
Set Forced Door
Time
45 # time # 0 # ✱ ✱ (10 to 990 seconds)
Change Keypad
Parameters
32 # parameter # value # ✱ ✱
(refer to page 20 for details)
Reset Defaults Only
40 # 00000 # 00000 # ✱ ✱
Erase Users and
Reset Default
Settings
46 # 00000 # 00000 # ✱ ✱