DN-6862  08/07/01  Page 1 of 3
ing control relays, the LED indicates ON/OFF).
On the ACM-24AT, each LED point is individually color-pro-
grammable. On ACM-48A, each column of 24 LED points
can be color-configured using a DIP switch.
Applications
The ACS Series provides arrays of LEDs to indicate point
status and, in some versions, switches to control the state
of output circuits.
Installation
The ACS Series annunciator and control subsystems use
modular hardware assemblies which allow the custom
configuration of the annunciator panel to fit the individual
job requirements.
Standard backboxes and mounting hardware schemes,
including special remote cabinets, allow the annunciators
to be constructed and configured with other NOTIFIER
system components.
When used with the NFS-640, AM2020, AFP1010, AFP-400,
or AFP-300, the ACS modules are used for manual selec-
General
The ONYX Series ACS Annunciators provide a modular
line of products for annunciation and control of the
NOTIFIER ONYX Series NFS-640 Intelligent Fire Alarm
Control Panel and NCA Network Control Annunciator, as
well as NOTIFIERs AM2020, AFP1010, AFP-400, AFP-300,
and AFP-200 fire control panels. The ACS line provides
arrays of LEDs to indicate point status and, in some ver-
sions, switches to control the state of output circuits. These
ACS units use a serial interface and may be located at dis-
tances of up to 6,000 feet (1,828.8 meters) from the panel.
Features
Speaker control mode for use with XPIQ and the follow-
ing panels: NFS-640, AM2020, AFP1010, AFC-600, AFP-
400, AFP-300. Enables the ACS to control operation of
groups of multi-channels mapped to groups of multi-
speakers.
Compatible with existing annunciators.
Color-programmable LEDs.
On-board end-of-line resistors can be enabled/disabled
by setting a switch.
Alarm/Circuit On and Trouble LED per-point option or
more dense Alarm-only option.
Touch-pad control switch option for remote control of
system relays; or silence, reset, and evacuate.
LEDs may be programmed to display status of indicat-
ing circuits or control relays as well as system status
conditions.
Fan Control (manual/automatic) option for the AM2020
and AFP1010.
System Trouble LED indicator.
On-Line/Power LED indicator.
Alarm and trouble resound with flash of new conditions.
Local sounder for both alarm and trouble conditions with
silence/acknowledge button (program options).
Serial EIA-485 interface for reduced installation cost.
May be powered by 24 VDC from the panel or by remote
power supplies.
Efficient switched-power converter reduces power con-
sumption.
Microprocessor-controlled electronics, fully supervised.
Slip-in custom labels, lettered with standard typewriter
or LabelEase program.
Plug-in terminal blocks for ease of installation and ser-
vice.
Trouble monitor option for remote power supplies.
Construction
The ACS modules are provided in two basic controller
modules, each with its expander module. The ACM-24AT
provides 24 annunciation and control points per module,
each with a red, green, or yellow Alarm/Circuit On LED, a
yellow Trouble LED, and a touch-key switch. The ACM-48A
provides 48 annunciation points per module, each with a
red, green, or yellow Alarm/Circuit On LED (for annunciat-
August 7, 2001
Section: Annunciator Control Systems
DN-6862  D-95
ACS Series Annunciators
ACM/AEM-24AT, ACM/AEM-48A
Made in the U.S.A.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
12 Clintonville Road, Northford, Connecticut 06472
ONYX is a trademark of NOTIFIER.
ACM/AEM-48AACM/AEM-24AT
6862at24.wmf
6862a48.wmf
S635

Other manuals for Notifier ACS Series

Question and Answer IconNeed help?

Do you have a question about the Notifier ACS Series and is the answer not in the manual?

Summary

General Information

Key Features

Lists operational capabilities and characteristics of the ACS Series Annunciators.

System Construction

Module Components

Describes the physical build and components of the ACS modules.

Applications Overview

Use Cases

Outlines the primary uses and scenarios for the ACS Series.

Installation Guidelines

Installation Overview

Details the process and considerations for installing ACS annunciator subsystems.

Product Line Details

ACM;AEM-24 AT and ACM;AEM-48 A Modules

Details the ACM/AEM-24AT and ACM/AEM-48A control and expander modules.

Surface Mount Backboxes (ABS Series)

Describes ABS-1B, ABS-1TB, and ABS-2B surface mount enclosures for ACS modules.

Flush Mount Backboxes (ABF Series)

Describes ABF-1B and ABF-2B flush mount enclosures for ACS modules.

Additional Backboxes and Accessories

Specific Backbox Types (ABF-1 DB, ABF-2 DB, ABS-4 D)

Semi-flush and surface mount backboxes for ACS Series Annunciators.

Dress Panels and Blank Module

ADP-4B Dress Panel, DP-DISP Dress Panel-Display, and BMP-1 Blank Module.

Key Switch and Phone Jack

AKS-1B Key Switch for security and APJ-1B Phone Jack for Firefighters Telephone.

Agency Listings and Approvals

Listing Agencies and Approvals

Refers to listing agencies and file numbers for ACS Series products.

A;E Specifications

Specification Information

Directs users to contact NOTIFIER for Architectural/Engineering specifications.

Overview

The ONYX™ Series ACS Annunciators are a modular line of products designed for annunciation and control within Notifier's ONYX™ Series NFS-640 Intelligent Fire Alarm Control Panel and NCA Network Control Annunciator, as well as older Notifier fire control panels like the AM2020, AFP1010, AFP-400, AFP-300, and AFP-200. These devices provide arrays of LEDs to indicate point status and, in some versions, include switches to control output circuits. They utilize a serial interface, allowing them to be located up to 6,000 feet (1,828.8 meters) from the main panel, which significantly reduces installation costs.

Function Description

The ACS Series annunciators serve as remote interfaces for monitoring and controlling various aspects of a fire alarm system. They display the status of indicating circuits, control relays, and system status conditions through a series of LEDs. Depending on the model, they can also include touch-key switches for remote control of system relays, silence, reset, and evacuate functions.

A key feature is the speaker control mode, compatible with XPIQ and several Notifier panels (NFS-640, AM2020, AFP1010, AFC-600, AFP-400, AFP-300). This mode enables the ACS units to control groups of multi-channels mapped to specific groups of speakers, facilitating targeted audio evacuation or communication.

The system supports both per-point annunciation for alarm/circuit on and trouble conditions, or a more dense alarm-only option, allowing for flexible configuration based on specific monitoring needs. LEDs can be programmed to display the status of individual circuits or control relays, as well as general system status conditions. For panels like the AM2020 and AFP1010, a fan control option (manual/automatic) is available, further extending the control capabilities of the annunciator.

Communication with the host Fire Alarm Control Panel is established via an EIA-485 multi-drop loop, which simplifies wiring and reduces installation costs. This serial interface allows for efficient data exchange between the annunciators and the main panel. The ACS system can support up to 32 remote annunciators, each with a capacity of 96 points, for a total system capacity of 3072 points, depending on the FACP's capabilities. The NCA (Network Control Annunciator) can utilize the full 96 points.

Usage Features

The ACS modules are designed for user-friendly operation and configuration. The ACM-24AT provides 24 annunciation and control points, each with a red, green, or yellow Alarm/Circuit On LED, a yellow Trouble LED, and a touch-key switch. Each LED point on the ACM-24AT is individually color-programmable, offering granular control over visual indicators. The ACM-48A, on the other hand, provides 48 annunciation points per module, each with a red, green, or yellow Alarm/Circuit On LED, and its columns of 24 LED points can be color-configured using a DIP switch.

Both the ACM-24AT and ACM-48A include a System Trouble LED indicator and an On-Line/Power LED indicator for quick system status checks. They also feature a local piezo sounder with a silence/acknowledge switch, providing audible indication for alarm and trouble conditions. New conditions trigger an alarm and trouble resound with a flash, ensuring that operators are promptly alerted.

The modules are compatible with existing annunciators, allowing for seamless integration into existing Notifier systems. Color-programmable LEDs enhance visual clarity and allow for customized status indications. On-board end-of-line resistors can be enabled or disabled via a switch, simplifying wiring and configuration.

For remote annunciation, the modules can be mounted in specialized ABF or ABS boxes. Control switch key locks (AKS-1/-1B) and phone jacks (APJ-1/-1B) are available for enhanced security and communication. The system can be powered by 24 VDC from the main panel or by remote power supplies, offering flexibility in installation. An efficient switched-power converter reduces power consumption, contributing to energy efficiency.

Maintenance Features

The ACS Series annunciators are designed with ease of installation and maintenance in mind. All field-wiring terminations use removable, compression-type terminal blocks, which simplifies wiring, circuit testing, and future servicing. This plug-in terminal block design allows for quick and secure connections.

The modules feature microprocessor-controlled electronics that are fully supervised, ensuring reliable operation and early detection of potential issues. Slip-in custom labels, which can be lettered with a standard typewriter or using the LabelEase program, allow for clear identification of each point, simplifying troubleshooting and operation.

For systems requiring remote power, a trouble monitor option is available for remote power supplies, providing supervision of external power sources. Retrofitting ACS Series annunciators into existing systems is straightforward, though software upgrades may be necessary. For AM2020 or AFP1010 panels, a SIB-2048(A)/SIB-NET Serial Interface Board is required for compatibility.

The modular hardware assemblies allow for custom configuration of the annunciator panel to fit individual job requirements. Standard backboxes and mounting hardware schemes, including special remote cabinets, enable the annunciators to be constructed and configured alongside other Notifier system components, streamlining installation and maintenance within a unified system. The various backbox options (ABS-1B, ABS-1TB, ABS-2B, ABF-1B, ABF-2B, ABF-4B, ABF-1DB, ABF-2DB, ABS-4D) provide flexibility for surface or flush mounting and accommodate different numbers of modules, ensuring a suitable enclosure for every application. The BMP-1 Annunciator Blank Module is available to cover unused module positions, maintaining a clean and professional appearance.

Notifier ACS Series Specifications

General IconGeneral
TypeFire Alarm Control Panel
ZonesVaries by model (programmable)
CommunicationRS-485
DisplayLCD
Operating Voltage120 VAC or 240 VAC, 50/60 Hz
Alarm ContactsForm-C
Trouble ContactsForm-C
DimensionsVaries by model
ComplianceUL
AnnunciationRemote Annunciators Available
ListingUL 864