DN-6862  08/07/01  Page 1 of 3
ing control relays, the LED indicates ON/OFF).
On the ACM-24AT, each LED point is individually color-pro-
grammable. On ACM-48A, each column of 24 LED points
can be color-configured using a DIP switch.
Applications
The ACS Series provides arrays of LEDs to indicate point
status and, in some versions, switches to control the state
of output circuits.
Installation
The ACS Series annunciator and control subsystems use
modular hardware assemblies which allow the custom
configuration of the annunciator panel to fit the individual
job requirements.
Standard backboxes and mounting hardware schemes,
including special remote cabinets, allow the annunciators
to be constructed and configured with other NOTIFIER
system components.
When used with the NFS-640, AM2020, AFP1010, AFP-400,
or AFP-300, the ACS modules are used for manual selec-
General
The ONYX Series ACS Annunciators provide a modular
line of products for annunciation and control of the
NOTIFIER ONYX Series NFS-640 Intelligent Fire Alarm
Control Panel and NCA Network Control Annunciator, as
well as NOTIFIERs AM2020, AFP1010, AFP-400, AFP-300,
and AFP-200 fire control panels. The ACS line provides
arrays of LEDs to indicate point status and, in some ver-
sions, switches to control the state of output circuits. These
ACS units use a serial interface and may be located at dis-
tances of up to 6,000 feet (1,828.8 meters) from the panel.
Features
Speaker control mode for use with XPIQ and the follow-
ing panels: NFS-640, AM2020, AFP1010, AFC-600, AFP-
400, AFP-300. Enables the ACS to control operation of
groups of multi-channels mapped to groups of multi-
speakers.
Compatible with existing annunciators.
Color-programmable LEDs.
On-board end-of-line resistors can be enabled/disabled
by setting a switch.
Alarm/Circuit On and Trouble LED per-point option or
more dense Alarm-only option.
Touch-pad control switch option for remote control of
system relays; or silence, reset, and evacuate.
LEDs may be programmed to display status of indicat-
ing circuits or control relays as well as system status
conditions.
Fan Control (manual/automatic) option for the AM2020
and AFP1010.
System Trouble LED indicator.
On-Line/Power LED indicator.
Alarm and trouble resound with flash of new conditions.
Local sounder for both alarm and trouble conditions with
silence/acknowledge button (program options).
Serial EIA-485 interface for reduced installation cost.
May be powered by 24 VDC from the panel or by remote
power supplies.
Efficient switched-power converter reduces power con-
sumption.
Microprocessor-controlled electronics, fully supervised.
Slip-in custom labels, lettered with standard typewriter
or LabelEase program.
Plug-in terminal blocks for ease of installation and ser-
vice.
Trouble monitor option for remote power supplies.
Construction
The ACS modules are provided in two basic controller
modules, each with its expander module. The ACM-24AT
provides 24 annunciation and control points per module,
each with a red, green, or yellow Alarm/Circuit On LED, a
yellow Trouble LED, and a touch-key switch. The ACM-48A
provides 48 annunciation points per module, each with a
red, green, or yellow Alarm/Circuit On LED (for annunciat-
August 7, 2001
Section: Annunciator Control Systems
DN-6862  D-95
ACS Series Annunciators
ACM/AEM-24AT, ACM/AEM-48A
Made in the U.S.A.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
12 Clintonville Road, Northford, Connecticut 06472
ONYX is a trademark of NOTIFIER.
ACM/AEM-48AACM/AEM-24AT
6862at24.wmf
6862a48.wmf
S635

Other manuals for Notifier ACS Series

Question and Answer IconNeed help?

Do you have a question about the Notifier ACS Series and is the answer not in the manual?

Notifier ACS Series Specifications

General IconGeneral
TypeFire Alarm Control Panel
ZonesVaries by model (programmable)
CommunicationRS-485
DisplayLCD
Operating Voltage120 VAC or 240 VAC, 50/60 Hz
Alarm ContactsForm-C
Trouble ContactsForm-C
DimensionsVaries by model
ComplianceUL
AnnunciationRemote Annunciators Available
ListingUL 864

Summary

General Information

Key Features

Lists operational capabilities and characteristics of the ACS Series Annunciators.

System Construction

Module Components

Describes the physical build and components of the ACS modules.

Applications Overview

Use Cases

Outlines the primary uses and scenarios for the ACS Series.

Installation Guidelines

Installation Overview

Details the process and considerations for installing ACS annunciator subsystems.

Product Line Details

ACMAEM-24 AT and ACMAEM-48 A Modules

Details the ACM/AEM-24AT and ACM/AEM-48A control and expander modules.

Surface Mount Backboxes (ABS Series)

Describes ABS-1B, ABS-1TB, and ABS-2B surface mount enclosures for ACS modules.

Flush Mount Backboxes (ABF Series)

Describes ABF-1B and ABF-2B flush mount enclosures for ACS modules.

Additional Backboxes and Accessories

Specific Backbox Types (ABF-1 DB, ABF-2 DB, ABS-4 D)

Semi-flush and surface mount backboxes for ACS Series Annunciators.

Dress Panels and Blank Module

ADP-4B Dress Panel, DP-DISP Dress Panel-Display, and BMP-1 Blank Module.

Key Switch and Phone Jack

AKS-1B Key Switch for security and APJ-1B Phone Jack for Firefighters Telephone.

Agency Listings and Approvals

Listing Agencies and Approvals

Refers to listing agencies and file numbers for ACS Series products.

AE Specifications

Specification Information

Directs users to contact NOTIFIER for Architectural/Engineering specifications.

Related product manuals