DN-6862  08/07/01  Page 1 of 3
ing control relays, the LED indicates ON/OFF).
On the ACM-24AT, each LED point is individually color-pro-
grammable. On ACM-48A, each column of 24 LED points
can be color-configured using a DIP switch.
Applications
The ACS Series provides arrays of LEDs to indicate point
status and, in some versions, switches to control the state
of output circuits.
Installation
The ACS Series annunciator and control subsystems use
modular hardware assemblies which allow the custom
configuration of the annunciator panel to fit the individual
job requirements.
Standard backboxes and mounting hardware schemes,
including special remote cabinets, allow the annunciators
to be constructed and configured with other NOTIFIER
system components.
When used with the NFS-640, AM2020, AFP1010, AFP-400,
or AFP-300, the ACS modules are used for manual selec-
General
The ONYX Series ACS Annunciators provide a modular
line of products for annunciation and control of the
NOTIFIER ONYX Series NFS-640 Intelligent Fire Alarm
Control Panel and NCA Network Control Annunciator, as
well as NOTIFIERs AM2020, AFP1010, AFP-400, AFP-300,
and AFP-200 fire control panels. The ACS line provides
arrays of LEDs to indicate point status and, in some ver-
sions, switches to control the state of output circuits. These
ACS units use a serial interface and may be located at dis-
tances of up to 6,000 feet (1,828.8 meters) from the panel.
Features
Speaker control mode for use with XPIQ and the follow-
ing panels: NFS-640, AM2020, AFP1010, AFC-600, AFP-
400, AFP-300. Enables the ACS to control operation of
groups of multi-channels mapped to groups of multi-
speakers.
Compatible with existing annunciators.
Color-programmable LEDs.
On-board end-of-line resistors can be enabled/disabled
by setting a switch.
Alarm/Circuit On and Trouble LED per-point option or
more dense Alarm-only option.
Touch-pad control switch option for remote control of
system relays; or silence, reset, and evacuate.
LEDs may be programmed to display status of indicat-
ing circuits or control relays as well as system status
conditions.
Fan Control (manual/automatic) option for the AM2020
and AFP1010.
System Trouble LED indicator.
On-Line/Power LED indicator.
Alarm and trouble resound with flash of new conditions.
Local sounder for both alarm and trouble conditions with
silence/acknowledge button (program options).
Serial EIA-485 interface for reduced installation cost.
May be powered by 24 VDC from the panel or by remote
power supplies.
Efficient switched-power converter reduces power con-
sumption.
Microprocessor-controlled electronics, fully supervised.
Slip-in custom labels, lettered with standard typewriter
or LabelEase program.
Plug-in terminal blocks for ease of installation and ser-
vice.
Trouble monitor option for remote power supplies.
Construction
The ACS modules are provided in two basic controller
modules, each with its expander module. The ACM-24AT
provides 24 annunciation and control points per module,
each with a red, green, or yellow Alarm/Circuit On LED, a
yellow Trouble LED, and a touch-key switch. The ACM-48A
provides 48 annunciation points per module, each with a
red, green, or yellow Alarm/Circuit On LED (for annunciat-
August 7, 2001
Section: Annunciator Control Systems
DN-6862  D-95
ACS Series Annunciators
ACM/AEM-24AT, ACM/AEM-48A
Made in the U.S.A.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
12 Clintonville Road, Northford, Connecticut 06472
ONYX is a trademark of NOTIFIER.
ACM/AEM-48AACM/AEM-24AT
6862at24.wmf
6862a48.wmf
S635
Question and Answer IconNeed help?

Do you have a question about the Notifier ACM-24AT and is the answer not in the manual?

Notifier ACM-24AT Specifications

General IconGeneral
TypeAnnunciator
Number of Zones24
Power Supply24 VDC
Maximum Current Draw100 mA
Temperature Range32°F to 120°F (0°C to 49°C)
Humidity Range10% to 93% non-condensing
CompatibilityNotifier Fire Alarm Control Panels
DescriptionThe ACM-24AT is a remote annunciator for use with Notifier fire alarm control panels. It provides a visual indication of alarm status for up to 24 zones.

Summary

General Information

Product Features

Construction Overview

ACS Series Product Line

ACM-24AT Annunciator Control Module

Module with 24 points, color-programmable LEDs, touch-pad switches, and local piezo sounder.

AEM-24AT Annunciator Expander Module

Expands ACM-24AT by 24 points, identical in size and appearance to ACM-24AT.

ACM-48A Annunciator Control Module

Module with 48 points, color-programmable LEDs, system trouble and online/power LEDs.

AEM-48A Annunciator Expander Module

Expands ACM-48A by 48 points, identical in appearance to ACM-48A.

ABS-1B Surface Backbox

Surface-mount enclosure for one annunciator module, with 1/2" conduit knockouts.

ABS-1TB Surface Backbox

Surface-mount backbox for one ACS Annunciator, with increased depth for APJ-1B and AKS-1B.

ABS-2B Surface Backbox

Surface box for mounting one ACM-24AT/AEM-24AT or ACM-48A/AEM-48A combination.

ABF-1B Flush Mount Box

Flush-mount enclosure for a single annunciator module, includes trim plate.

ABF-2B Flush Mount Box

Flush mount box for two annunciator modules, includes trim plate.

ABF-4B Flush Mount Box

Flush mount box for one to four annunciator modules, includes trim plate.

Additional Backboxes and Panels

ABF-1DB/ABF-2DB/ABS-4D Backboxes

Semi-flush-mount backboxes for ACS Series Annunciators, with smoked glass door and keylock.

ADP-4B Annunciator Dress Panel

Dress panel for cabinet mounting of one to four modules on CAB-4 Series cabinets.

DP-DISP Dress Panel-Display

Dress panel for mounting one to four modules in CAB-4 Series backbox.

BMP-1 Annunciator Blank Module

Flat black dress plate to cover unused module positions in backbox or ADP-4B.

AKS-1B Annunciator Key Switch

Key switch for access security on ACM/AEM-24AT, compatible with ABS-1TB.

APJ-1B Annunciator Phone Jack

Phone jack for Fire Fighters Telephone (FFT-7), includes mounting hardware.

Agency Listings and Approvals

Architectural/Engineering Specifications

Related product manuals