ID50 Series Panel - Operating Manual
Automatic Alarms - What to do
6997-264-000-8, Issue 8
January 2007
Recommended operator actions:
Note: In the recommended operator actions described below
only MUTE BUZZER and END DELAY are selectable
at Access Level 1. The operation of EXTEND DELAY,
EVACUATE, SILENCE, RESOUND and RESET must
only be possible at access Level 2, in accordance with
the requirements of EN54:Part 2.
1 Operate the MUTE BUZZER pushbutton to silence
the panel’s internal buzzer.
2 Follow prescribed instructions for evacuation of
premises, notification of Fire Brigade and investigation
of source of fire.
3 If additional sounder operations are required to
achieve a complete and immediate evacuation of the
premises, press the END DELAY /EVACUATE
pushbutton (needs access level 2). This will cause
the internal buzzer to resound, so press the MUTE
BUZZER pushbutton to silence.
4 When more than one fire Alarm condition is present,
it is possible to manually scroll through all logged Fire
Alarm conditions using the ‘
2
/
8
’ arrows.
Note: With multiple alarms, the LCD displays the first
alarm event.
5 When evacuation of the premises is achieved, or at
the direction of an authorised person, the Alarm
Sounders may be silenced by pressing the
SILENCE / RESOUND pushbutton.
Note: The SOUNDERS SILENCED LED illuminates if
this option was configured during panel
commissioning. The default function for this LED
is PRE-ALARM.
6 To re-start the sounders, press the
SILENCE / RESOUND pushbutton. You must wait at
least 10 seconds after having originally silenced the
sounders before resounding them. If the SOUNDERS
SILENCED LED option was configured during
commissioning to illuminate, this will now extinguish.
7 When the cause of the alarm has been removed and
call points and input devices have been locally reset,
the system may be returned to ‘Status: NORMAL* by
pressing the RESET pushbutton.
* Unless the Site name menu was edited during
commissioning - refer to Section 4.1.1 Liquid crystal
Display.
3
4
7
Status: NORMAL
Sat 01/12/2001 00:00:00
5
6
1
EN54-2: 7.6.1, 7.8, 8.7.1,
9.1.2
Ensure EN54 compliance
for access to controls.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier ID50 SERIES and is the answer not in the manual?

Notifier ID50 SERIES Specifications

General IconGeneral
BrandNotifier
ModelID50 SERIES
CategoryFire Alarms
LanguageEnglish

Related product manuals