54 NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14
Power Supply Calculations Calculating the System Current Draws
Category
Calculation Column 1
Primary, Non-Fire Alarm
Current (amps)
Calculation Column 2
Primary, Fire Alarm
Current (amps)
Calculation Column 3
Secondary, Non-Fire Alarm
Current (amps)
Qty X [current draw]= Total Qty X [current draw]= Total Qty X [current draw]= Total
NFS-320/E
# NACs in use (0, 1, 2, 3 or 4)
*
CPS-24/E
KDM-R2 (Backlight on)
1
[]
n/a
[]
x [0.250] =
x [0.035]
n/a
x [0.100]=
1
[]
n/a
[]
x [0.250] =
x [0.035]
n/a
x [0.100]=
1
[]
1
[]
x [0.250] =
x [0.035]
x [0.040]
x [0.100]=
SLC loop
: 1 x [0.200]= 1 x [0.200]= 1 x [0.200]=
NCA, NCA-2 Back-light ON
NCA, NCA-2 Back-light OFF
NCM-W/F
HS-NCM-W/MF/SF/WMF/WSF/MFSF
TM-4
DPI-232 (Refer to manual**)
[]
[]
[]
[]
[]
[]
x [0.400]=
x [0.200]=
x [0.110]=
x [0.400]=
x [0.110]=
x [ ]=
[]
[]
[]
[]
[]
[]
x [0.400]=
x [0.200]=
x [0.110]=
x [0.400]=
x [0.175]=
x [ ]=
[]
[]
[]
[]
[]
[]
x [0.400]=
x [0.200]=
x [0.110]=
x [0.400]=
x [0.110]=
x [ ]=
APS-6R
ACPS-2406, ACPS-610
[]
[]
x [0.025]=
x [0.0013]=
ACM-24AT
ACM-48A
AEM-24AT
AEM-48A
[]
[]
[]
[]
x [0.016]=
x [0.016]=
x [0.002]=
x [0.002]=
[]
[]
[]
[]
x [0.070]=
x [0.070]=
x [0.056]=
x [0.056]=
[]
[]
[]
[]
x [0.016]=
x [0.016]=
x [0.002]=
x [0.002]=
Maximum number of LEDs illuminated on
these annunciators during non-fire
conditions:
[ ] x [0.0054]= [ ] x [0.0054]=
AFM-16AT, AFM-32A
ACM-16AT, ACM-32A
AEM-16AT, AEM-32A
[]
[]
[]
x [0.040]=
x [0.040]=
x [0.002]=
[]
[]
[]
x [0.056]=
x [0.056]=
x [0.018]=
[]
[]
[]
x [0.040]=
x [0.040]=
x [0.002]=
AFM-16A
ACM-8R (refer to manual**)
LDM (refer to manual**)
FDU-80
LCD-80
LCD2-80
[]
[]
[]
[]
[]
x [0.025]=
x [ ]=
x [ ]=
x [0.0643]=
x [0.100]=
[]
[]
[]
[]
[]
x [0.065]=
x [ ]=
x [ ]=
x [0.0643]=
x [0.100]=
[]
[]
[]
[]
[]
x [0.025]=
x [ ]=
x [ ]=
x [0.0643]=
x [0.050]=
FZM-1, MMX-2 Auxiliary power [ ] x [0.0115]= [ ] x [0.090]= [ ] x [0.0115]=
RPT-W, RPT-WF, RPT-F
RPT-485W, RPT-485WF
[ ] x [0.017]= [ ] x [0.017]= [ ] x [0.017]=
UDACT Communicator
UDACT-2 Communicator
NFV-25/50 (see manual**)
[]
[]
[]
x [0.040]=
x [0.052]=
x [ ]=
[]
[]
[]
x [0.100]=
x [0.087]=
x [ ]=
[]
[]
[]
x [0.040]=
x [0.052]=
x [ ]=
FWSG (only if powered by the FWSG 24V
connections TB:A2 and TB:A3)
[ ] x [0.040]= [ ] x [0.040]= [ ] x [0.040]=
Four-Wire Smoke Detectors
[]
[]
x [ ]=
x [ ]=
[]
[]
x [ ]=
x [ ]=
[]
[]
x [ ]=
x [ ]=
Power Supervision Relay
EOLR-1
[ ] x [0.020]= [ ] x [0.020]= [ ] x [0.020]=
Notification Appliance powered from Main
Power Supply
**
[]
[]
x [ ]=
x [ ]=
DHX-501, FSD-751RPFSD-751RPL(Duct
Detectors with internal relays)
Refer to installation document
[]
[]
x [ ]=
x [ ]=
[]
[]
x [ ]=
x [ ]=
[]
[]
x [ ]=
x [ ]=
CHG-120 Battery Charger [ ] x [0.060]=
Local Energy Municipal Box [ ] x [ ]=
Compatible Devices not listed above
††
[]
[]
x [ ]=
x [ ]=
[]
[]
x [ ]=
x [ ]=
[]
[]
x [ ]=
x [ ]=
Sum each column for totals Primary, non-alarm: Primary, alarm: Secondary, non-alarm:
Table A.2 System Draw Current Calculations
* Maximum current draw for all NACs plus DC output from TB10 and TB2 is 3.0 A during standby.
Value represents an SLC’s maximum current draw. Refer to device datasheets for individual current draws.
The total regulated load current supplied to four-wire smoke detector and power supervision relays cannot exceed 1.25 A.
** Enter the total notification appliance draw from the Main Power Supply, excluding the current from APS-6R supplies. Refer to Device Compatibility Document.
†† Refer to manual and/or Device Compatibility Document. See Table 1.1, “Reference Documentation,” on page 8 for specific documentation part numbers.