EasyManua.ls Logo

Notifier NFS-320C - 5: System Cabinet

Notifier NFS-320C
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NFS-320/E/C Installation Manual — P/N 52745:M2 7/1/14 15
System Components System Overview
2.2.5 System Cabinet
The control panel is factory installed in its backbox. The lockable door is hinged on the left and
opens a full 180 degrees. Mounting methods include surface-mounting or semi-flush mounting on a
wall between 16 inch (40.64 cm) on-center studs. A trim ring option is available for semi-flush
mounting.
External measurements:
Backbox: 18.12 in. (46.025 cm) width;
18.12 in. (46.025 cm) height;
5.81 in. (14.76 cm) depth.
Door: 18.187 in. (46.195 cm) width;
18.40 in. (46.736 cm) height;
0.75 in. (1.905 cm) depth.
When using trim ring TR-320, mount backbox with at least 1 inch (2.54 cm) between wall surface
and front of backbox, to allow door to open fully past the trim ring. The TR-320 molding width is
0.905 in. (2.299 cm).
Additional Options
The NFS-320/E/C control panel provides space for one or two additional option boards to be
installed, as shown in Figure 3.3 on page 21. The NFS-320C fulfills ULC annunciation
requirements; see NFS-320C Canadian Applications Addendum for details. A variety of compatible
annunciators are available with their own backboxes; see Section 2.3, “Compatible Equipment”.