Nu-Air Ventilation Systems Inc. - HRV Operating & Installation Manual
Rev. 2.3 Aug. 19, 2014 - 3 -
VENTILATION PERFORMANCE
ENERGY PERFORMANCE
EXT.
STATIC
GROSS AIR FLOW
SUPPLY
NET
POWER
SENSIBLE
APPARENT
PRESSURE
SUPPLY
EXHAUST
TEMP.
AIR FLOW
CONSUMED
RECOVERY
SENSIBLE
in wg (Pa)
cfm (l/s)
cfm (l/s)
ºF (ºC)
cfm (l/s)
Watts
EFFICIENCY
EFFECTIVENESS
0.1 (25)
180 (84)
193 (91)
+32 (0)
61 (29)
54
63
75
0.2 (50)
165 (78)
175 (82)
+32 (0)
85 (40)
66
62
72
0.3 (75)
151 (71)
159 (75)
+32 (0)
114 (54)
94
61
70
0.4 (100)
137 (65)
144 (68)
0.5 (125)
123 (58)
130 (61)
13 (-25)
62 (29)
58
65
78
0.6 (150)
109 (51)
116 (55)
0.7 (175)
94 (44)
103 (48)
1. PERFORMANCE RATINGS & PHYSICAL DATA
Model: NU165
ELECTRICAL: 120V/1/60 Hz. 128W, 1.1A