© 2022 nVent
89215758
- 35 -
REFRIGERANT PROPERTIES CHART (R 134A)
°F °C Pressure °F °C Pressure
-40 -40 -14.7 60 15.6 58
-35 -37.2 -12.3 65 18.3 64
-30 -34.4 -9.7 70 21.1 71.5
-25 -31.7 -6.8 75 23.9 78
-20 -28.9 -4 80 26.7 86.7
-15 -26.1 0 85 29.4 95
-10 -23.3 2 90 32.2 105
-5 -20.6 4 95 35 113.3
0 -17.8 7.5 100 37.8 125
5 -15 9 105 40.6 135
10 -12.2 12 110 43.3 146.7
15 -9.4 15 115 46.1 157.5
20 -6.7 18.5 120 48.9 170
25 -3.9 22 125 51.7 185
30 -1.1 26 130 54.4 197.5
35 1.7 30 135 57.2 213.3
40 4.4 35 140 60 230
45 7.2 40 145 62.8 246.7
50 10 45.5 150 65.6 263.8
55 12.8 51.5
FUNCTIONAL DATA
Unit
Evaporator. Air
In(°F)
Amps(A)
Condenser
Delta(°F)
Evaporator
Delta(°F)
N360616GXXX
65-80 4.6-6.2 14-30 12-26
80-100 5.0-7.4 16-35 14-31
N360626GXXX
65-80 2.5-3.4 17-35 11-23
80-100 2.8-4.0 19-39 13-30
N360646GXXX
65-80 1.3-1.8 12-23 13-15
80-100 1.4-1.9 17-26 9-19
N360816GXXX
65-80 5.6-7.6 12-29 14-30
80-100 6.2-9.1 16-34 16-36
N360826GXXX
65-80 3.8-5.0 13-31 8-20
80-100 4.1-5.6 17-42 11-22
N360846GXXX
65-80 1.4-1.9 12-28 10-22
80-100 1.5-2.1 15-35 12-31