BA_OTE 3+4_Endkunde_EN_V03_20170726.docx Page 39 of 52
Fig. 12: Flow temperature course for floor screed heat up
The settings for set value increase or equilibrium phase must be adjusted by a
professional partner after consultation with the floor screed professional! In-
correct settings can lead to damage to the floor screed. OCHSNER accepts no li-
ability for this!
Heating up the floor screed with heat pumps is NOT permitted for earth-coupled systems
(heat pumps type GMSW or GMDW). Due to the heating up, above average amounts of
energy could be extracted from the ground, which could lead to sustained damage to the
whole heat pump heating system. OCHSNER accepts no liability for this!
TV [°C]
t
Flow temperature course
Set value decrease:
e.g.: 6 K/day
Set value increase: e.g.: 3 K/day
Set value
Equilibrium phase: 30°C
Equilibrium phase: e.g.: 3 days
Start temperature:
Flow set value at
start of heat up
NOTE