Oilon GP-1000 M - User Manual

Oilon GP-1000 M
106 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
M4263 2206EN
14 February 2022
Operation and maintenance manual
Burner models: GP-1000 M - 1200 M
Burner equipment: WDx00, ME comb. head, FGR
Read these instructions carefully before installation, use, or maintenance

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Oilon GP-1000 M and is the answer not in the manual?

Overview

This document describes the Oilon GP-1000 M - 1200 M series burners, which are automatic forced draught burners suitable for various heating appliances, including warm and hot water boilers, steam boilers, hot air generators, and process heating. They are designed to operate in furnaces with high back pressure.

Function Description:

The Oilon GP-1000 M - 1200 M burners are designed for efficient combustion, primarily using natural gas. They can also be adapted for other gases, provided their composition is known and the burner manufacturer is consulted. The burner control system, specifically the WiseDrive 100/200, handles all operational sequences automatically and includes safety functions to stop the burner in case of failure. The WD200 system allows for O2 module integration to enhance combustion efficiency. The burner control adjusts the fuel and air ratio, as well as solenoid valves, to match capacity demands.

Important Technical Specifications:

  • Burner Models: GP-1000 M and GP-1200 M.
  • Capacity:
    • GP-1000 M: 6.8–42.0 MMBtu/h
    • GP-1200 M: 8.3–50.4 MMBtu/h
  • Burner Motor:
    • 3~ 208–600 V 60 Hz with frequency converter.
    • GP-1000 M: 50 hp output, 55.9 A/460 V current, 2,970 rpm speed.
    • GP-1200 M: 60 hp output, 66.7 A/460 V current, 2,970 rpm speed.
  • Control Unit: WDx00.
  • Weight (Burner only): GP-1000 M: 1,720 lb; GP-1200 M: 1,830 lb.
  • Turndown Ratio (gas): 1:5 (100...20%).
  • Gas Inlet Pressure (max.): Natural gas: 40 - 200 "W.C.; LPG: 48 - 200 "W.C.
  • Max. Demand for Combustion Air (gas use): 13.5 cfh/MBtu.
  • Efficiency (natural gas): 35.31 ft³n/h ≈ 13.5 MBtu efficiency, when heat value is 961.91 Btu/ft³.
  • Performance (natural gas): 950 - 1050 btu/sc.ft.
  • Control Voltage: 115 V (-15%...+10%) 50 Hz / 60 Hz 1-phase.
  • Motor Voltage Options: 220 V, 400 V, 460 V, 575 V (all 60 Hz 3-phase).
  • Sound Pressure Level (LpfA): 84.0 ± 0.5 dB.
  • Sound Power Level (LwA): 101.5 ± 0.5 dB.
  • Burner Control (LMV5...):
    • Mains voltage: 120 VAC -15/+10 %.
    • Locking during undervoltage: < 96 VAC.
    • Ambient temperature range: -4...+140 °F.
  • Display and Operating Unit (AZL...):
    • Supply voltage: 24 VDC –15/+10 %.
    • Ambient temperature range: -4...+140 °F.
  • O2 Module (PLL52...):
    • Mains voltage, sensor heating: 110 VAC –15/+10 %.
    • Mains voltage: 2 x 12 VAC.
    • Ambient temperature range: -4...+140 °F.
  • Oxygen Sensor (QGO20...):
    • Measuring cell: ceramic zirconium dioxide.
    • Mains voltage, measuring cell heating: 110 VAC -15/+10 %.
    • Measuring cell temperature: 1292 °F ±122 °F.
    • Measuring range: 0.2…20.9 % O2.
    • Max. temperature, flue gas: +572 °F.
  • Flame Detector (QRI/F200K):
    • Supply voltage: 14 VDC ±5% (operation), 21 VDC ±5% (testing).
    • Signal voltage: 0–5 VDC.
    • Connected detector cable max. length: 5.9 ft (QRI), 328 ft (auxiliary detector cable).

Usage Features:

  • Flue Gas Recirculation (FGR): Optional feature to reduce NOx content by recirculating a proportion of flue gas back into the combustion chamber, lowering flame temperature. The amount of FGR is adjustable via a throttle valve and control panel settings.
  • WiseDrive System: A comprehensive control and safety system that includes burner control, electronic fuel/air ratio, gas valve proving, capacity controller, fan frequency converter control (WD200), residual oxygen control (WD200), boiler cold start thermal shock protection, fuel flow meter (WD200), burner efficiency measuring (WD200), start-up and running time counters, fault and lockout history, real-time clock, and a bus interface.
  • Operating and Display Unit (AZL): Used for monitoring and adjusting settings, with menus available in multiple languages. It has an internal memory backed up by a battery for storing burner control parameters.
  • Servomotors: Drive fuel regulators and other actuating devices, with precise angular adjustment and torque.
  • Frequency Converter (WD200): Controls the fan motor speed to adjust air pressure according to burner capacity. Features include alarm contact for safety stops and control via a 0/4…20 mA signal.
  • O2 Module (WD200): Measures residual oxygen in flue gases to monitor and optimize combustion efficiency. Can be connected with combustion air and flue gas temperature sensors to calculate and display efficiency.
  • Cold Start Thermal Shock Protection: Protects the boiler from thermal stress by starting with a small load and gradually increasing it as the boiler warms up.
  • Boiler Temperature Limiting: Limits boiler temperature using the burner control, either with the main temperature sensor or a separate one.

Maintenance Features:

  • Annual Checks:
    • Burner head extension.
    • Diffuser disc and burner adjustments.
    • Ignition cable condition.
    • Ignition electrodes (cleanliness and position).
    • Flame detector (position, condition, cleanliness).
    • Filters (clean/replace).
    • Air dampers fixing screws and servomotor axle lock.
    • Hoses, pipes, and joints for leaks.
    • Adjustment rod joints (lubricate if adjustable combustion head).
    • Burner cleanliness (dust and moisture).
    • Boiler room fresh air ventilator (open).
    • Combustion characteristics (flue gas measurements).
  • Safety Device Testing: Regular testing of flame detector, differential pressure switch, gas pressure switches, gas shut-off valves, servomotors, O2/CO trim control (if equipped), and boiler safety devices.
  • Parameter Backup: Ability to back up burner parameters from the display and operating unit to the LMV5x control unit.
  • Troubleshooting: Comprehensive troubleshooting guide for start failures, motor failures, lack of fan air pressure, leakage test failures, no electric arc for ignition, flame formation issues, lockout after flame establishment, flame monitoring faults, and poor combustion.
  • Spare Parts: Emphasizes using only original spare parts and providing burner type and serial number when ordering.
  • Documentation: Manuals and electrical diagrams should be kept available near the device.

Oilon GP-1000 M Specifications

General IconGeneral
BrandOilon
ModelGP-1000 M
CategoryBurner
LanguageEnglish