PARAMETER AND SETTING
Field parameter table (Primary parameters)
Code Description Remarks Setting Range Default
HIAL High limit alarm
Alarm on when PV>HIAL
alarm off when PV<HIAL- AHYS
-999~+3000 3000
LoAL Low limit alarm
Alarm on when PV<LoAL;
alarm off when PV>LoAL + AHYS
-999~+3000 -999
HdAL
Deviation high
alarm
Alarm on when PV-SV>HdAL;
alarm off when PV-SV<HdAL - AHYS
-999~+3000 3000
LdAL
Deviation low
alarm
Alarm on when PV-SV<LdAL;
alarm off when PV-SV>LdAL + AHYS
-999~+3000 -999
Loc Parameter Lock
Loc
Auto
Tuning
SV
Primary
Parameter
Secondary
Parameter
0
X
1
X X
2
X X X
3
X X X X
808
: allow to modify data or execute AT
X : not allow to modify data or execute AT
0~255 0