Modbus Parameter settings
10
Automatic Baudrate Detection:
Can be configured YES or NO
Supported baudrates:
2400, 4800, 9600, 19.2k, 38.4k, 57.6k, 115.2k bps
Parity Mode:
Even, Odd or None parity
Stop Bits:
1 or 2 stop bits
Response delay:
0...1000 ms (0 ms = default)
Modbus slave addressing range:
1 - 247 (247 = default address)
Modbus Parameter Storage:
Saved in non-volatile memory in the DRST-CM device (Factory Default Values
are marked in bold)
Modbus RTU segment line termination:
A 120 Ohm resistor should be installed on both ends of a RS485 Modbus RTU segment loop to prevent
signal echoes from corrupting data on the line.
DRST-CM Modbus parameter settings