Series Meters Quick Start Guide
15
Complete Menu Structure
5.2 Programming Mode Menu (PRoG)
The following table maps the Programming Mode (PRoG) navigation:
Level
2
Level
3
Level
4
Level
5
Level
6
Notes
SP1
____
Process goal for PID, default goal for oN.oF
SP2
ASbo
Setpoint 2 value can track SP1, SP2 is an absolute value
dEVI
SP2 is a deviation value
ALM.1
Note: This submenu is the same for all other Alarm configurations.
tyPE
oFF
ALM.1 is not used for display or outputs
AboV
Alarm: process value above Alarm trigger
bELo
Alarm: process value below Alarm trigger
HI.Lo.
Alarm: process value outside Alarm triggers
bANd
Alarm: process value between Alarm triggers
Ab.dV
AbSo
Absolute Mode; use ALR.H and ALR.L as triggers
d.SP1
Deviation Mode; triggers are deviations from SP1
d.SP2
Deviation Mode; triggers are deviations from SP2
CN.SP
Tracks the Ramp & Soak instantaneous setpoint
ALR.H
____
Alarm high parameter for trigger calculations
ALR.L
____
Alarm low parameter for trigger calculations
A.CLR
REd
Red display when Alarm is active
AMbR
Amber display when Alarm is active
GRN
Green display when Alarm is active
dEFt
Color does not change for Alarm
HI.HI
oFF
High High / Low Low Alarm Mode turned off
oN
____
Offset value for active High High / Low Low Mode
LtCH
No
Alarm does not latch
yES
Alarm latches until cleared via front panel
botH
Alarm latches, cleared via front panel or digital input
RMt
Alarm latches until cleared via digital input
CtCL
N.o.
Output activated with Alarm
N.C.
Output deactivated with Alarm
A.P.oN
yES
Alarm active at power on
No
Alarm inactive at power on
dE.oN
____
Delay turning off Alarm (sec), default = 1.0
dE.oF
____
Delay turning off Alarm (sec), default = 0.0
oUt2
oUt2 is replaced by output type
oUt3
oUt3 is replaced by output type (1/8 DIN can have up to 6)
PId.S
ACtN
RVRS
Increase to SP1 (i.e., heating)
dRCt
Decrease to SP1 (i.e., cooling)
A.to
____
Set timeout time for autotune
AUto
StRt
Initiates autotune after StRt confirmation