11
61F-GP-N@
Automatic Water Supply Control Automatic Drainage Control
Automatic Water Supply and Drainage Control Compact, Plug-in Type
61F-GP-N8
Dimensions:
page 14
Water supply
source
MCCB
RS
M
T
Commercial Voltage
61F-GP-N8
PS-3S
Stop
E2
E3
E1
P
Start
8 V
0 V
U
U
U
24 V
Control
circuit
(See note.)
218 7
3456
Water
tank
Contac-
tor
Power
supply
Motor
protection
relay
Note: Be sure to ground the common Electrode E3 (the
longest Electrode).
Connection Sockets
PF083A (Front-connecting)
PL08 (Rear-connecting)
• Connect terminal 2 to the contactor’s coil terminal.
Note: The power supply depends on the specifications of the
model.
Connections
Reservoir
MCCB
RS
M
T
61F-GP-N8
P
8 V
0 V
U
U
U
24 V
(See
note.)
3456
PS-3S
E2
E3
E1
Start
Stop
218 7
Control circuit
Contac-
tor
Power
supply
Motor
protection
relay
Waste-
water
tank
Commercial Voltage
Note: Be sure to ground the common Electrode E3 (the
longest Electrode).
Connection Sockets
PF083A (Front-connecting)
PL08 (Rear-connecting)
• Connect terminal 3 to the contactor’s coil terminal.
Note: The power supply depends on the specifications of the
model.
Connections
E
1
E
2
E
3
P
Water
supply
(Indicator ON)
Pump OFF
Pump ON
(Indicator OFF)
The pump stops when the water level reaches E1 (indicator ON)
and starts when the water level drops below E
2 (indicator OFF).
Principles of Operation
E1
E2
E3
Water drainage
(Indicator ON)
Pump OFF
Pump ON
(Indicator OFF)
P
Principles of Operation
The pump starts when the water level reaches E
1 (indicator ON)
and stops when the water level drops below E
2 (indicator OFF).