5. Measuring the backup time
(3) Calculate the initial value of the backup time for the total capacity of the connected devices from the
graph below.
Graph of backup time (graph of initial values for products that have not been used)
The smaller the capacity of connected devices becomes, the longer the backup time becomes.
120
110
100
90
80
70
60
50
40
30
20
10
0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
1600 1700 1800 1900 2000 2100
Backuptime
(20°C,initialvalue)
BU1002SW
BU3002SW
BU1002SW+
BUM100S
BU3002SW+
BUM300S
(Minutes)
Powerconsumption
ofconnecteddevices(W)
* These backup times are for reference only. Times may vary according to battery life and external
environmental conditions (temperature, etc.).
Time unit: Minutes
Model 20W 50W 100W 200W 300W 400W 500W 700W 1000W 1400W
BU1002SW 180 120 60 35 20 15 10 5
- -
720 420 240 120 80 60 50 30
- -
BU1002SW+
BUM100S
Model 200W 400W 600W 800W 1000W 1200W 1400W 1600W 1800W 2000W 2100W
BU3002SW 92 46 30 20 15 12 10 8
7 5.5 5
BU3002SW
340 175 115 85 62 49 43 37
31 26 24
+ BUM300S