This manual provides important safety-related information. Thoroughly read and understand
this manual before installing and using the product.
Keep this manual in a convenient location so that you can refer to it whenever necessary.
BU1002SW/BU3002SW
Uninterruptible Power Supply (UPS/200 to 240V specifi cations)
Instruction Manual
-
バッテリ
 交換
バッテリ
 増設
ブザー停止/テス
電源出力
バイパス
運転
BU1002SW
-
バッテリ
 交換
バッテリ
 増設
ブザー停止/テス
電源出力
バイパス
運転

Table of Contents

Questions and Answers

  • S
    susanlittleJul 31, 2025
    What to do if the Omron UPS status indicator shows blank and beeps?
    • S
      Stacey MoralesJul 31, 2025
      If the status indicator on your Omron UPS shows “ ” and the beeper is sounding at 0.5-second intervals, it means there are too many devices connected. Reduce the number of connected devices until “ ” is displayed on the status indicator.
  • T
    Travis MillerAug 4, 2025
    How to troubleshoot an Omron BU1002SW UPS that does not turn on?
    • J
      Jennifer RojasAug 4, 2025
      If your Omron UPS doesn't operate and the LED display doesn't light up, even when connected to a wall outlet and the power switch is ON: * First, ensure the AC input plug is securely connected to the commercial power. * Second, check the AC input overcurrent protection. For BU1002SW models, if the black INPUT PROTECTION button has popped up, disconnect devices, press the INPUT PROTECTION switch, and turn the power switch back on. For BU3002SW models, turn ON the AC input overcurrent protection switch on the back of the unit and then turn the power switch back ON. If the status indicator still doesn't display properly, there may be a problem with the unit.
  • M
    Michael AllisonAug 8, 2025
    Why does my Omron UPS switch frequently without power failure?
    • A
      aromeroAug 8, 2025
      If your Omron UPS switches frequently even without a power failure, it may be due to variations in the input power or noise distorting the voltage waveform. Try these steps: * Change the wall outlet to which the UPS is connected, choosing one away from equipment that consumes large power. * Avoid connecting many devices to a plug strip or extension cord connected to the UPS, especially if the cable is long or thin.
  • M
    Michelle MeyersAug 12, 2025
    What to do if Omron BU1002SW backup is not working?
    • R
      Rebecca JohnsonAug 12, 2025
      If backup is not possible with your Omron UPS and the computer stops during a power failure, the battery might not be sufficiently charged. Charge the battery for at least 8 hours before performing the test. If you have an additional battery connected, charge it for 24 hours. You can charge the battery by connecting the AC input plug of the UPS to a wall outlet.
  • X
    xnashAug 16, 2025
    How to fix an abnormal display on an Omron BU1002SW UPS?
    • S
      Sarah CooperAug 16, 2025
      If the display on your Omron UPS is abnormal (unstable, showing white lines, or with increased noise), it's likely due to internal noise. Consider these solutions: * Ground all devices connected to the UPS by using 3-pin plugs or connecting their Grounding Terminal to the Grounding Terminal of a wall outlet. * Rearrange power cords if they are long or placed closely, and reposition the UPS and connected devices. * If the UPS or connected devices are in a metal rack, try grounding the rack itself.
  • R
    richardcohenAug 21, 2025
    What does it mean when Omron UPS status indicator blinks and beeps continuously?
    • C
      Clayton PriceAug 21, 2025
      If the status indicator on your Omron UPS blinks “ ” and the beeper sounds continuously, the output has stopped due to exceeded connection capacity. Turn OFF all power to the unit and connected devices, reduce the number of connected devices, and then turn the power back ON to the unit and connected devices. Check if " " is displayed on the status indicator.
  • A
    amoralesAug 26, 2025
    What does it mean when the battery replacement lamp blinks on Omron BU1002SW?
    • T
      thamiltonAug 26, 2025
      If the battery replacement lamp blinks and the beeper sounds at 2-second intervals on your Omron UPS, it means that the auto battery test or self-diagnostic test determined that the battery is dead or the overcurrent protection switch on the rear panel of the additional battery unit got turned OFF when connecting an additional battery unit. If it is not ON, the auto battery test may falsely detect a deteriorated battery.

Summary

Introduction

Product Features and Usage Notes

Explains UPS features, important usage guidelines, and limitations.

Important Safety Instructions

Instructions, Symbols, and Specifications

Covers saving instructions, safety symbols, battery voltage, temperature, and environment.

Procedure from Installation to Operation

Safety Precautions

General Warnings and Cautions

Highlights critical safety hazards and provides initial cautions for installation.

Installation and Connection Safety

Usage and Environmental Safety

Battery Replacement Safety

1 Preparation

1-1 Unpacking and Checking Contents

Instructions for unpacking the UPS and verifying all package contents are included and undamaged.

1-3 Name of each part

Rear View Components

1-4 Explanation of symbols used on unit

2 Installation and Connection

2-1 Precautions and notes on installation and connection

Provides essential safety precautions and notes for installing and connecting the UPS.

Installation and Connection Safety

Installation and Connection Safety

Notes on Installation and Connection

3 Operation

3-1 Precautions and notes for operation

Details safety precautions for operating the UPS, including handling plugs and liquids.

4 UPS functions

4-1 Suspending a beep

Instructions on how to temporarily silence audible beeps from the UPS.

4-2 Self-diagnosis test

Explains how to perform a self-diagnosis test to check for battery deterioration or failures.

4-3 Description of the auto battery test function

4-4 Changing the setting of the functions

Setting Switch Function List

Setting Switch Details

Auto Startup Mode Setting

2 UPS operation mode settings

2-1 Settable items and explanations

Details the settable operation modes and their explanations.

5 Measuring the backup time

5-1 How to measure backup time

Provides a step-by-step guide to measure the UPS backup time accurately.

6 Maintenance and Inspection

6-1 Checking the battery

Details methods for checking battery life, condition, and replacement timing.

6-2 Replacing the battery

6-3 Replacing the fan

3-3 Interpreting beeps and displays

6-4 Cleaning

7 Using the UPS monitoring software and contact signal

UPS monitoring software

Details compatibility and usage of UPS monitoring software for various operating systems.

7-1 When using the included UPS monitoring software to perform auto shutdown

7-2 When performing auto-save functions using the UPS service in Windows Server 2003;XP;2000 + UPS service driver

7-3 When performing auto-save functions using the standard UPS service in Windows Server 2003;XP;2000;NT

7-4 Contact signal

4. Contact Signal Connector

5. Remote ON;OFF connector

8. Example of the use of the Contact Signal circuit

9. Precautions and notes for the use of the Contact Signal

8 Using an SNMP;Web card

8-1 Adding an SNMP;Web card

Instructions for installing an SNMP/Web card into the UPS unit.

8-2 SNMP;Web card outline

9 Extending the backup time

9-1 Connecting an additional battery unit

Provides instructions for connecting an optional battery unit to extend backup time.

10 Troubleshooting

Problem Checks and Remedies

Lists common UPS problems and their corresponding checks and remedies.

Reference

A. Specifications

Provides detailed technical specifications for both BU1002SW and BU3002SW models.

B. Dimensions

C. Circuit block diagram

Omron BU1002SW Specifications

General IconGeneral
CategoryUPS
BrandOmron
ModelBU1002SW
Capacity1000 VA
Wattage600 W
Form FactorTower
TopologyLine Interactive
Frequency50/60 Hz
Battery TypeSealed Lead Acid
Communication InterfaceUSB
Safety CertificationsCE, RoHS
Output ConnectionsIEC C13 x 4
Backup TimeVaries by load
Transfer Time4ms typical
Operating Temperature0 to 40°C
Operating Humidity0 to 90% non-condensing
Output Voltage220-240V