4-2
Fail-safe Circuits
WARNING
Provide safety measures in external circuits to ensure safety in the system if an ab-
normality occurs due to malfunction of the system due to other external factors af
fect-
ing operation. Not doing so may result in serious accidents due to incorrect operation.
Emergency stop circuits, interlock circuits, limit circuits, and similar safety measures
must be provided in external control circuits.
You must take fail-safe measures to ensure safety in the event of incorrect, missing,
or abnormal signals caused by broken signal lines, momentary power interruptions,
or other causes.
The use of an Uninterruptible Power Supply (UPS) allows normal operation to con-
tinue even if a momentary power interruption occurs, possibly resulting in the recep-
tion of an erroneous signal from an external device affected by the momentary pow-
er failure. Take external fail-safe measures. Where necessary, monitor the power
supply voltage on the system for external devices and use it as an interlock condi-
tion.
Unintended behavior may occur if an error occurs in the internal memory of the
product. As a countermeasure for these problems, external safety measures must
be provided to ensure safe operation of the system.
The Controller will turn OFF all outputs from Output Units in the following cases.
The slaves will operate according to the settings in the slaves.
a) If a power supply error occurs
b) If the power supply connection becomes faulty
c) If a CPU Unit error (watchdog timer error) or CPU Unit reset occurs
d) If a major fault level Controller error occurs
e) While the Controller is on standby until RUN mode is entered after the power is
turned ON
f) If a system initialization error occurs
As a countermeasure for these problems, external safety measures must be provided
to ensure safe operation of the system.
To ensure safe use of the Controller, correctly make the limit settings for the posi-
tion, speed, acceleration, jerk, current, and following error, as well as the encoder
loss detection.
For devices that move in a vertical direction, use a motor brake to prevent them
from falling down when the servo control is stopped.
4 Mounting and Wiring
4-4
CK3E-series Programmable Multi-Axis Controller Users Manual Hardware (I610)

Table of Contents

Other manuals for Omron CK3E Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CK3E Series and is the answer not in the manual?

Omron CK3E Series Specifications

General IconGeneral
BrandOmron
ModelCK3E Series
CategoryController
LanguageEnglish

Related product manuals