65
1
Select Master in the Solution
Explorer of Power PMAC IDE.
Display the Slave to Slave tab
page.
2
Expand Slave_1001
[NX-ECC203]Module 1
(NX-SL3500).Input Data Set 1
in Inputs.
Expand Slave_1001
[NX-ECC203]Module 2
(NX-SID800).Output Data Set 1
in Outputs.
Select an Inputs item, then
select the corresponding
Outputs item and click >>.
Associate the following items:
Inputs Outputs
Variable 0
FSoE Master CMD
Variable 1 Safety Output 1st Word
Variable 2 FSoE Master CRC_0
Variable 3 FSoE Master Conn_ID
3
Expand
Slave_1001
[NX-ECC203]Module 1
(NX-SL3500).Input Data Set 1
in Inputs.
Expand Slave_1001
[NX-ECC203]Module 3
(NX-SOD400).Output Data Set
1 in Outputs.
Select an Inputs item, then
select the corresponding
Outputs item and click >>.
Associate the following items:
Inputs Outputs
Variable 4 FSoE Master CMD
Variable 5 Safety Output 1st Word
Variable 6 FSoE Master CRC_0
Variable 7 FSoE Master Conn_ID