CompoWay/F
2.3 Detailed Description of the Services
2-19
(2) Response Code
Normal Completion
Error Occurred
09 Auto/Manual Switch 00: Automatic mode
01: Manual mode
0B Parameter Initialization 00: Initialize to defaults
0C Alarm Latch Cancel 00: Alarm 1 latch cancel
01: Alarm 2 latch cancel
02: Alarm 3 latch cancel
03: HB alarm latch cancel
04: HS alarm latch cancel
05: OC alarm latch cancel
0F: All alarm latch cancel
0D SP Mode 00: Local SP Mode
01: Remote SP Mode
0E Invert Direct/Reverse
Operation
00: Not invert
01: Invert
11 Program Start 00: Reset
01: Start
12 Infrared Communication
Use
00: OFF
01: ON
Response code Name Description
0000 Normal completion No errors were found.
Response code Error name Cause
1001 Command too long The command is too long.
1002 Command too short The command is too short.
1100 Parameter error Command code and related
information are wrong.
2203 Operation error • The Communications Writ-
ing parameter is set to “OFF”
(disabled). The command is
received regardless of the
Communications Writing
parameter setting (ON/OFF).
• Processing could not be per-
formed. For details, see (3)
Operation Commands and
Precautions below.
• EEPROM error
Command
code
Command content Related Information