Modbus
5.4 Detailed Description of the Services
5-17
RUN/STOP
Set control to “run” or “stop” with the related information setting. The
setting can be accepted in both setup area 0 and setup area 1. An
operation error will occur, however, if RUN/STOP is set for an event
input.
Bank Change
Select a bank from 0 to 7 with the related information setting. The
setting can be accepted in both setup area 0 and setup area 1. An
operation error will occur in the following situations.
When AT is being executed
When a bank change is set for the event input (Bank Numbers Used
parameter setting > 0)
When the program pattern is set to any setting other than OFF, the
bank number must be between 00 and the bank set for the Valid
Program Bank, and a parameter error will occur if the related infor-
mation setting exceeds the bank set for the Valid Program Bank
parameter setting.
AT Execute/Cancel
Set AT (auto-tuning) to “execute” or “cancel” with the related information
setting. This command can be accepted in setup area 0 only. An
“operation error” will be generated in the following instances:
When the RUN/STOP parameter is set to “stop”
When the command is executed in “setup area 1”
When ON/OFF control is being used
When 40% AT is specified during 100% AT execution.
When 100% AT is specified during 40% AT execution.
In addition, a parameter error will occur if 40% AT is specified during
heating and cooling control or during position-proportional floating
control.
Note: If the same type of AT execution is specified during AT execution
(e.g., if 100% AT execution is specified during 100% AT
execution), the AT will not be restarted and the operation will end
in normal completion with no processing.
Write Mode
Set either “backup mode” or “RAM write mode” with the related infor-
mation setting. The setting can be accepted in both setup area 0 and
setup area 1.
The number of EEPROM (non-volatile memory) write operations is
limited. Therefore, use RAM write mode when frequently overwriting
data.

Table of Contents

Other manuals for Omron E5CN-H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CN-H and is the answer not in the manual?

Omron E5CN-H Specifications

General IconGeneral
BrandOmron
ModelE5CN-H
CategoryController
LanguageEnglish

Related product manuals