F3SJ-A
11
Response Time
Note:
Use the following expressions for series connection.
For 2-set series connection:
Response time (ON to OFF): Response time of the 1st unit + Response time of the 2nd unit - 1 (ms), Response time (OFF to ON): Response time calculated by the above x 4 (ms)
For 3-set series connection:
Response time (ON to OFF):
Response time of the 1st unit + Response time of the 2nd unit + Response time of 3rd unit - 5 (ms), Response time (OFF to ON): Response time calculated by the above x 5 (ms)
(
For models with the "-TS" suffix, multiply the response time obtained by the above x 5 (ms), or use 200 ms, whichever is less.)
For 4-set series connection:
Response time (ON to OFF): Response time of the 1st unit + Response time of the 2nd unit + Response time of the 3rd unit + Response time of the 4th unit - 8 (ms)
Response time (OFF to ON): Response time calculated by the above x 5 (ms)
Cable Extension Length
Total cable extension length must be no greater than the lengths described below.
When the F3SJ and an external power supply are directly connected, or when the F3SJ is connected to a G9SA-300-SC.
When connected to the F3SP-B1P
Note: Keep the cable length within the rated length. Failure to do so is dangerous as it may prevent safety functions from operating normally.
* The F39-A01P@-PAC Dedicated External Indicator Set uses LEDs. Refer to the cable extension lengths for "Not using incandescent lamp".
Model
PNP output
F3SJ-A@@@@P14 F3SJ-A@@@@P20 F3SJ-A@@@@P30 F3SJ-A@@@@P55
NPN output
F3SJ-A@@@@N14 F3SJ-A@@@@N20 F3SJ-A@@@@N30 F3SJ-A@@@@N55
Accessories
Instruction manual, standard mounting bracket (F39-LJ1 bracket for top/bottom mounting), mounting brackets
(intermediate) (*),
error mode label, Quick Installation Manual (QIM)
*. Number of intermediate brackets depends on protective height of F3SJ.
• For protective height from 600 to 1,130 mm : 1 set for each of the emitter and receiver is included
• For protective height from 1,136 to 1,658 mm : 2 sets for each of the emitter and receiver are included
• For protective height from 1,660 to 2,180 mm : 3 sets for each of the emitter and receiver are included
• For protective height from 2,195 to 2,500 mm : 4 sets for each of the emitter and receiver are included
Applicable standards
IEC 61496-1, EN 61496-1, UL 61496-1, Type 4 ESPE (Electro-Sensitive Protective Equipment)
IEC 61496-2, EN 61496-2, UL 61496-2, Type 4 AOPD (Active Opto-electronic Protective Devices)
IEC 61508-1 to -3, EN 61508-1 to -3 SIL3
ISO 13849-1: 2006, EN ISO 13849-1: 2008 (PLe/Safety Category 4)
UL 508, UL 1998, CAN/CSA C22.2 No.14, CAN/CSA C22.2 No.0.8
Model Protected Height (mm) Number of Beams
Response time ms (ON to OFF)
Response time ms (OFF to ON)
F3SJ-A@14 Series
245 to 263 26 to 28 11 44
281 to 389 30 to 42 12 48
407 to 497 44 to 54 13 52
515 to 605 56 to 66 14 56
623 to 731 68 to 80 15 60
767 to 983 84 to 108 17.5 70
1,055 to 1,271 116 to 140 20 80
F3SJ-A@20 Series
245161040
275 to 425 18 to 28 11 44
455 to 635 30 to 42 12 48
665 to 815 44 to 54 13 52
845 to 995 56 to 66 14 56
1,025 to 1,205 68 to 80 15 60
1,235 to 1,505 82 to 100 17.5 70
F3SJ-A@30 Series
245 to 395 10 to 16 10 40
420 to 720 17 to 29 11 44
745 to 1,045 30 to 42 12 48
1,070 to 1,295 43 to 52 13 52
1,395 to 1,620 56 to 65 14 56
1,745 to 1,995 70 to 80 15 60
2,120 to 2,495 85 to 100 17.5 70
F3SJ-A@55 Series
270 to 770 6 to 16 10 40
820 to 1,420 17 to 29 11 44
1,470 to 2,070 30 to 42 12 48
2,120 to 2,470 43 to 50 13 52
Condition 1 set 2 sets 3 sets 4 sets
Using incandescent lamp for auxiliary output and external indicator output
45 m 40 m 30 m 20 m
Not using incandescent lamp * 100 m 60 m 45 m 30 m
Condition 1 set 2 sets 3 sets 4 sets
Using incandescent lamp for external indicator output 2 40 m 30 m 25 m 20 m
Using incandescent lamp for external indicator output 1
60 m 45 m 30 m 20 m
Using incandescent lamp for auxiliary output 1
Not using incandescent lamp * 100 m 60 m 45 m 30 m