H5BR
H5BR
161
Ratings
Rated supply voltage 100 to 240 VAC, 50/60 Hz
24 VAC/12 to 24 VDC (permissible ripple: 20% max.)
Operating voltage range 85% to 110% of rated voltage
Power consumption Approx. 8 VA at 50 Hz, 240 VAC; approx. 5 W at 24 VDC
Reset and control signals Min. pulse width 1 ms/20ms selectable
Batch count reset and gate Min. pulse width: Approx. 20 ms
Key protect Response time: 1 s
One-shot time 0.1 to 99.9 s or hold
Power reset (except A-3, b-1, and F mode) Min. power opening time: 0.5 s
Signal, reset, gate, batch count reset inputs No-voltage input
ON impedance: 1 k
$
max. (Approx. 2 mA when 0
$
)
ON residual voltage:2 V max.
OFF impedance: 100 k
$
min.
Key protect input No-voltage input
ON impedance: 1 k
$
max. (Approx. 2 mA when 0
$
)
ON residual voltage: 1 V max.
OFF impedance: 100 k
$
min.
Control outputs
Contacts: 5 A at 250 VAC, resistance load (cos
%
=1)
Transistor output: Open collector 100mA at 30 VDC max. residual voltage 2 V
max. (Approx. 1 V)
External power supply 80 mA, 12 VDC
!
10% (5% ripple max.)
Ambient temperature -10
"
Cto55
"
C (with no icing)
Storage temperature -25
"
Cto65
"
C (with no icing)
Ambient humidity 35% to 85%
Case Light gray
Characteristics
Repeat accuracy, setting error (including
temperature and voltage effects)
Power start:
!
0.01%
!
0.05 s max.
Control signal start:
!
0.005%
!
0.03 s max. *(rate for set value)
Insulation resistance 100 M
$
min. (at 500 VDC) (between current-carrying terminal and exposed
non-current-carrying metal parts, and between non-continuous contacts)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminal and
exposed non-current-carrying metal parts) for 100 to 240 VAC type
1,000 VAC for 24VAC/12 to 24 VDC type
Surge voltage 3 kV (between power terminals) for 100 to 240 VAC type, 1 kV for 24 VAC/12 to
24 VDC type
4.5 kV (between current-carrying terminal and exposed non-current-carrying
metal parts) for 100 to 240 VAC type, 1.5 kV for 24 VAC/12 to 24 VDC type
Noise immunity
!
2 kV (between power terminals) and
!
600 V (between input terminals),
square-wave noise by noise simulator (pulse width: 100 ns/1
&
s, 1-ns rise)
Static immunity Malfunction: 8 kV; destruction: 15 kV
Vibration Destruction 10 to 55 Hz with 0.75-mm single amplitude each in three directions
Malfunction 10 to 55 Hz with 0.5-mm single amplitude each in three directions
Shock Destruction 294 m/s
2
(30G) each in three directions
Malfunction 98 m/s
2
(10G) each in three directions
Life expectancy Mechanical 10 million operations min.
Electrical 100,000 operations min. (5 A at 250 VAC in load resistance)
Weight Approx. 270 g (9.6 oz)