H5S
5
■ Operation
Note: 1. Depending the operation, the following steps can be used for weekly programs.
Timer operation: 2 steps
Pulse-output operation: 1 step
Cyclic operation: 4 steps
2. When the season switching setting is not being used.
3. When the season switching setting is being used.
■ Operation Functions
Item Weekly 2-circuit Models
(H5S-W@2)
Yearly 2-circuit Models
(H5S-Y@2)
Yearly 4-circuit Models
(H5S-Y@4)
Operation method Digital quartz
Operation period 1 week (7 days) 1 year (with integrated calendar to 2099)
Display • Day, hrs (switchable between 24-hr indication and a.m./p.m. 12-hr indication), minutes, seconds
(0.00 to 23:59, 0.00 to 11:59 a.m., 0.00 to 11:59 p.m.)
• Digital indication by LCD (character height: 10 mm)
• Digital display of operation schedule during operation
• Timing chart display of operation schedule during operation
Min. setting unit 1 min
Number of
steps that
can be set
Weekly program
(See note 1.)
40 steps/circuit 48 steps/circuit (See note 2.)
24 steps/circuit (per season) (See
note 3.)
48 steps/circuit (See note 2.)
12 steps/circuit (per season) (See
note 3.)
Yearly program --- 4 yearly programs/circuit
Number of
settable yearly
temporary
holiday settings
--- 16
Item Weekly 2-circuit Models (H5S-W@2) Yearly 2-circuit Models (H5S-Y@2) Yearly 4-circuit Models (H5S-Y@4)
Weekly timer
operation
Controls the output according to the set time of ON and OFF.
• Min. setting unit: 1 min
• Multiple-day operation also possible.
Weekly pulse-
output
operation
Output turns ON for a fixed period (pulse width) at the set ON time.
• Pulse width: 1 to 59 s (in 1-s increments), or 1 to 60 min (in 1-min increments)
• The pulse width can be set for each step.
Weekly cyclic
operation
Repeatedly turns ON and OFF during the period from the cyclic start time to the stop time.
Independent ON- and OFF-time settings are possible.
• Min. setting unit: 1 min
Yearly timer
operation
--- Adds a yearly timer operation to the weekly timer program.
For details, refer to About Yearly Programs on page 18.
Yearly pulse-
output
operation
--- Adds a yearly pulse-output operation to the weekly pulse-output program.
For details, refer to About Yearly Programs on page 18.
Temporary
holiday setting
Sets temporary holidays (non-operating days) without having to revise the existing program.
For details, refer to Setting Temporary Holidays (Weekly) and Setting Temporary Holidays (Yearly) on page 20.
Day override
operation
Executes the operation for one day
temporarily on another day in the 7-day
period starting from the current day.
For details, refer to Day Override
Operation on page 21.
---
Program check Consecutively displays the days and times when the output is set to turn ON and OFF over the course of one week in the
sequence in which the Time Switch is to operate.
For details, refer to Program Check Function on page 21.
ON OFF
Timer operation
Pulse output operation
ON
Pulse width
Cyclic operation
StopStart
ON
OFF